Test User Interface and Electronic Control Board

If the User Interface does not turn on:
1. Make sure the unit has the proper voltage and that it is turned on.
Check power at Terminals L1 and L2. (Refer to Electronic Control
Board Identification, Figure 711)
2. Disconnect the User Interface's wire harness on the control board.
3. Using a voltmeter, check the outer pins on the user interface port
of the electronic control board . There should be 24VDC. (Refer to
Electronic Control Board Identification, Fig 711
4. If there is no voltage, replace the electronic control board.