Maytag MDE20CSTGW Installation Instructions Manual page 13

Commercial gas or electric dryer
Table of Contents

Advertisement

Available languages

Available languages

Connect Vent
1. If connecting to existing vent, make sure the vent is clean.
2. Using a 102 mm (4") clamp, connect vent to exhaust outlet
in dryer.
NOTE: Do not remove vent collar.
3. Tighten hose clamp with Phillips screwdriver.
4. Make sure the vent is secured to exhaust hood with
a 102 mm (4) clamp.
5. Move dryer into final position. Do not crush or kink vent.
Make sure dryer is level.
NOTE: Testing for proper ventilation should be done with a
Manometer. Minimum: 0.2 mm (0.01"). Maximum: 16 mm (0.6").
If an Exhaust Hood Cannot be Used
The outside end of main vent should have a sweep elbow
directed downward.
305 mm minimum
(12")*
* Minimum clearance above
any accumulation of snow,
ice, or debris such as leaves
If main vent travels vertically through the roof, rather than
through wall, install a 180° sweep elbow on end of vent at
least 610 mm (2 ft) above surface of roof.
Vent Collar
610 mm minimum
(24")*
The opening in wall or roof shall have a diameter 13 mm (1⁄2")
larger than vent diameter. Vent should be centered in opening.
Do not install screening over end of vent for best performance.
Multiple Dryer Venting
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 5,663 L/min (200 CFM) of
air per dryer. Large-capacity lint screens of proper design may
be used in main vent if checked and cleaned frequently. The
room where the dryers are located should have make-up air
equal to or greater than CFM of all the dryers in the room.
Back-draft dampers are available from your distributor and
should be installed in the vent of each dryer to keep exhausted
air from returning into dryers and to keep exhaust in balance
within main vent. Unobstructed return air openings are
required.
Although usually each single-load dryer should have an
unobstructed outdoor air opening of 155 cm
6.5 cm
[1 in
] per 252 kcal [1,000 B.T.U.]), common make-up
2
2
air openings are also acceptable. Set up common openings so
the make-up air is distributed equally to all of the dryers. Keep
in mind that the coverage area must be increased by 33% to
account for the use of registers or louvers over the openings.
Also, make-up air openings should not be installed near the
location where exhaust vents exit the building.
Each vent should enter the main vent at an angle pointing in
the direction of the airflow. Vents entering from the opposite
side should be staggered to reduce the exhausted air from
interfering with the other vents.
Air Flow
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning fluid fumes. Fumes
create acids which, when drawn through the dryer heating
units, can damage dryers and items being dried.
A clean-out cover should be located on the main vent for
periodic cleaning of the vent system.
NOTE: For more dryer venting information, please refer to
Whirlpool document W10100920.
(24 in
) (based on
2
2
30˚
maximum
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mde20mntgwMdg20cstgwMdg20mntgwMdg20mwtgw

Table of Contents