4.3 Address Mapping

For SI-W309 Series, the Modbus Address mappings and definitions are as
follows:
Address
0000
Firmware Version (00-20191126)
0010
Module Name (String="W309")
Baud Rate Setting
Code
Baud
0020
Code
Baud
Set Device ID
0030
Default: 01
Digital Output Channel 1 mode switch
1000
0: Lo, 1: Hi, 2: Clock
Digital Output Channel 2 mode switch
1001
0: Lo, 1: Hi, 2: Clock
Digital Output Channel 3 mode switch
1002
0: Lo, 1: Hi,2: Clock
Digital Output Channel 4 mode switch
1003
0: Lo, 1: Hi, 2: Clock
Digital Output y Channel 5 mode switch
1004
0: Lo,1: Hi, 2: Clock
Digital Output Channel 6 mode switch
1005
0: Lo, 1: Hi, 2: Clock
Digital Output Channel 7 mode switch
1006
0: Lo,1: Hi, 2: Clock
Digital Output Channel 8 mode switch
1007
0: Lo,1: Hi, 2: Clock
Power-on mode of Digital Output Channel 1
1040
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 2
1041
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 3
1042
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 4
1043
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 5
1044
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 6
1045
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 7
1046
0: Off, 1: On (Default: 0)
Power-on mode of Digital Output Channel 8
1047
0: Off, 1: On (Default: 0)
Set Digital Output Channel 1 High N millisecond in clock
1080
mode.
10~65535 (Default: 100)
SI-W309 SERIES USER MANUAL
Description
0
1
9600
19200
4
115200
Chapter 4 MODBUS RTU Protocol
2
3
38400
57600
Attr.
R
R
R/W
W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Page: 4-13