Address Mapping - Protech Systems SI-W509 User Manual

5 channels digital input and 6 channels relay output remote i/o module
Table of Contents

Advertisement

4.3 Address Mapping

For SI-W509 Series, the Modbus Address mappings and definitions are as
follows:
Address
0000
Firmware Version (00-20191126)
0010
Module Name (String="W509")
Baud Rate Setting
Code
0020
Baud
Code
Baud
Set Device ID
0030
Default: 01
Relay Channel 1 mode switch
1000
0: Lo, 1: Hi, 2: Clock
Relay Channel 2 mode switch
1001
0: Lo, 1: Hi, 2: Clock
Relay Channel 3 mode switch
1002
0: Lo, 1: Hi,2: Clock
Relay Channel 4 mode switch
1003
0: Lo, 1: Hi, 2: Clock
Relay Channel 5 mode switch
1004
0: Lo,1: Hi, 2: Clock
Relay Channel 6 mode switch
1005
0: Lo,1: Hi, 2: Clock
Power-on mode of Relay Channel 1
1040
0: Off, 1: On (Default: 0)
Power-on mode of Relay Channel 2
1041
0: Off, 1: On (Default: 0)
Power-on mode of Relay Channel 3
1042
0: Off, 1: On (Default: 0)
Power-on mode of Relay Channel 4
1043
0: Off, 1: On (Default: 0)
Power-on mode of Relay Channel 5
1044
0: Off, 1: On (Default: 0)
Power-on mode of Relay Channel 6
1045
0: Off, 1: On (Default: 0)
Set Relay Channel 1 High N millisecond in clock mode
1080
10~65535 (Default: 100)
Set Relay Channel 2 High N millisecond in clock mode
1082
10~65535 (Default: 100)
Set Relay Channel 3 High N millisecond in clock mode
1084
10~65535 (Default: 100)
Set Relay Channel 4 High N millisecond in clock mode
1086
10~65535 (Default: 100)
Set Relay Channel 5 High N millisecond in clock mode
1088
10~65535 (Default: 100)
SI-W509 SERIES USER MANUAL
Description
0
1
9600
19200
4
115200
Chapter 4 MODBUS RTU Protocol
2
3
38400
57600
Attr.
R
R
R/W
W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Page: 4-14