8.2.2

Quick wizard: Standard

Backup heater configuration (only for *9W model)
The backup heater in a *9W model is adapted to be connected to
most common European electricity grids. Besides hardware
configuration, the backup heater type must be set on the user
interface.
#
Code
[A.2.1.5]
[5-0D]
BUH type:
▪ 1 (1P,(1/1+2)): 6 kW 1~ 230 V (*9W)
▪ 3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W)
▪ 4 (3PN,(1/2)): 6 kW 3N~ 400 V (*9W)
▪ 5 (3PN,(1/1+2)): 9 kW 3N~ 400 V
(*9W)
Space heating/cooling settings
The system can heat up or cool down a space. Depending on the
type of application, the space heating/cooling settings must be made
accordingly.
#
Code
[A.2.1.7]
[C-07]
Unit control method:
▪ 0 (LWT control): Unit operation is
decided based on the leaving water
temperature regardless the actual
room temperature and/or heating or
cooling demand of the room.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat or
equivalent (e.g. heat pump convector).
▪ 2 (RT control): Unit operation is
decided
temperature of the user interface.
[A.2.1.B]
N/A
Only if there are 2 user interfaces (1
installed in the room, 1 installed at the
indoor unit):
▪ a: At unit
▪ b: In room as room thermostat
User interface location:
▪ At unit: the other user interface is
automatically set to In room and if RT
control is selected act as room
thermostat.
▪ In room (default): the other user
interface is automatically set to At unit
and if RT control is selected to act as
room thermostat.
ERHQ011~016BA + ERLQ011~016CA + EHVH/X16S18+26CA
Daikin Altherma - Low Temperature Split
4P313777-1C – 2012.11
Description
Description
based
on
the
ambient
a
b
#
Code
[A.2.1.8]
[7-02]
The system can supply leaving water to
up to 2 water temperature zones. During
configuration, the number of water zones
must be set.
Number of LWT zones:
▪ 0 (1 LWT zone)(default): Only 1
leaving water temperature zone. This
zone is called the main leaving water
temperature zone.
▪ a: Main LWT zone
▪ 1 (2 LWT zones): 2 leaving water
temperature zones. The zone with the
lowest leaving water temperature (in
heating) is called the main leaving
water temperature zone. The zone
with
temperature (in heating) is called the
additional leaving water temperature
zone. In practice, the main leaving
water temperature zone consists of
the higher load heat emitters and a
mixing station is installed to achieve
the desired leaving water temperature.
▪ a: Add LWT zone
▪ b: Main LWT zone
8 Configuration
Description
a
the
highest
leaving
water
a
b
Installer reference guide
35