System Installation
11-4. Power Control Module
Perform the following instructions for the peM.
a.
Remove the large and small panels
(seen from the rear of the
CPU Bay) from the PCM.
Save all hardware.
b.
Verify that jumpers have been correctly installed on TBI
and
TB2 as listed within figure 11-5.
c.
Have an
electrician perform
this step.
Connect primary ac
power cable
wires to the PCM line filter
terminals as shown
within figure 11-3.
d.
Remove all ac power plugs from all ac power service strips in
the equipment bays.
e.
Have an electrician perform this step.
Be sure the ac
power
at the
Computer
Mainframe
Power Panel 'and
PCM MAIN SYSTEM
POWER
and
PCU EXTENDED
SYSTEM
POWER circuit
breakers are
turned OFF.
Then,
connect the other end of the
primary ac
power cable
wired in step c
to
the isolation
transformer.
Then, turn ON the Computer Mainframe Power Panel main line.
f.
Use a suitable voltmeter to check voltages at each of the PCM
line filter terminals for correct value as listed within fig-
ure 11-3.
g.
Use a vol tmeter to check
the vol tage between ground and neu-
tral.
Voltage should not exceed I VAC (rros).
Use an oscil-
loscope to
check the ripple content of the
waveform between
ground and neutral (must not exceed 25 mv p-p).
h.
Check that the
EMERGENCY OFF pushbutton at the top
front of
the
CPU Bay is lighted.
If it is not, press it once.
If it
fails
to light,
an error
exists in
that circuit.
Do not
proceed further
until the error has
been corrected
and the
pushbutton will light.
i.
After confirming that the EMERGENCY OFF lamp lights,
set the
PCM MAIN SYSTEM
POw~R
circuit breaker ON.
Then, check the ac
power voltages at the ac power service strips throughout
the
cabinets as
shown
in figure 11-1.
If the voltages are in-
correct, set the PCM MAIN SYSTEM POWER and Computer Mainframe
Power Panel
circuit breakers OFF and check the ac power ser-
vice strip within the PDU against table 11-3.
If any errors
are found, correct them.
j.
Set the PCM MAIN SYSTEM POWER
circuit breaker to OFF and re-
place the access covers on all PDU's.
k.
Connect all fans,
card cages,
and other devices in the cab-
inets into
the appropriate ac
power service strips
and set
the PCM MAIN SYSTEM POWER circuit breaker to ON.
Check that
all fans in the system operate.
11-8