FINAL INSTALLATION PROCEDURES
Setting the External Static Pressure
Table 26: Mid-Static Ducted Indoor Unit External Static Pressure Setting Values Table.
Static Pressure (in. wg)
Model No. / Nominal
Capacity of System (Btu/h)
LHN098HV1
9,000
LHN128HV1
12,000
LHN188HV1
18,000
LHN248HV1
24,000
• To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other than
that listed in the table will not provide the desired combination.
• Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
66
0.1
0.16
Airflow Rate /
CFM
High
353.1
76
88
Mid
317.8
72
82
Low
282.5
68
78
High
494.4
91
98
Mid
423.8
82
92
Low
353.1
76
88
High
635.7
106
113
Mid
529.7
94
102
Low
423.8
82
92
High
706.3
122
128
Mid
547.4
103
110
Low
459.1
93
100
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
0.2
0.24
0.28
0.31
Setting Value (in. wg)
96
99
104
110
92
95
100
106
88
91
96
102
105
108
113
118
100
103
108
114
96
99
104
110
117
121
126
128
108
109
115
119
100
103
108
114
131
132
136
143
114
117
121
127
105
109
114
118
0.35
0.39
0.43
0.51
115
121
126
135
111
117
121
131
107
113
117
127
122
130
134
143
118
126
130
139
114
121
126
135
133
137
139
149
122
130
134
145
118
126
130
139
146
148
152
158
130
135
138
145
122
128
131
139
0.59
143
139
135
151
147
143
156
152
147
164
154
146