Section 8. Refrigerant Line Leak Check; Section 9. Evacuation; Section 10. Service Valves - Trane A4HP5 Installation And Operation Manual

Table of Contents

Advertisement

Section 8. Refrigerant Line Leak Check

8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.
STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks before continuing.

Section 9. Evacuation

9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation
are complete.
STEP 1 - Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the
vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 mi-
crons in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold
gauge set.

Section 10. Service Valves

10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere.
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve stem 1/4 turn counterclockwise to the fully open position.
STEP 3 - Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
10.2 Open the Liquid Service Valve
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until
the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in
abrupt release of system charge and may result in personal injury and /or property damage.
Important: Leak check and evacuation must be completed before opening the service valves.
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16" hex wrench into the stem and back out counterclockwise until valve stem just touches
the rolled edge (approximately five (5) turns.)
STEP 3 - Replace the valve cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
CAP
UNIT SIDE
OF VALVE
PRESSURE TAP PORT
GAS LINE CONNECTION
Gas Service Valve
88-A4HP5001-1D-EN
WARNING
!
1/4 TURN ONLY
COUNTERCLOCKWISE
FOR FULL OPEN
POSITION
VALVE STEM
Cap
Unit Side of
Service Valve
3/16" Hex Wrench
Rolled Edge to
Captivate Stem
Service Port
Liquid Service Valve
Hex Headed
Valve System
9 D

Advertisement

Table of Contents
loading

This manual is also suitable for:

A4hp5 seriesA4hp5018dA4hp5024dA4hp5030dA4hp5036dA4hp5042d ... Show all

Table of Contents