Trane A4HP5 Installation And Operation Manual page 14

Table of Contents

Advertisement

STEP 3 - Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to
stabilize before accurate measurements can be made.
STEP 4 - Measure the liquid line temperature and pressure at the outdoor unit's service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSIG
Final Subcooling Value = __________ º F
STEP 5 - Use the final subcooling value, refrigerant temperature and pressure from STEP 4, to determine the
proper liquid gage pressure using Table 14.2.
Example: Assume a 12º F Final Subcooling value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in the left column.
3. The Liquid Gage Pressure should be approximately 327 PSIG. (This is the shown as the intersection of
the Final Subcooling column and the Liquid Temperature row.)
STEP 6 - Adjust refrigerant level to attain proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
1. Connect gages to refrigerant bottle and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure matches the charging chart
Final Subcooling value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system
is properly charged.
2. Remove gages.
3. Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Curves in this document to verify typical performance.
14
R-410A REFRIGERANT CHARGING CHART
LIQUID
TEMP
(
°
F)
55
179
60
195
65
211
229
70
247
75
267
80
287
85
309
90
95
331
107 °F
100
355
105
381
110
407
115
435
120
464
125
495
Table 14.2
FINAL SUBCOOLING (
8
9
10
11
12
LIQUID GAGE PRESSURE (PSI)
182
185
188
191
198
201
204
208
215
218
222
225
232
236
240
243
251
255
259
263
271
275
279
283
291
296
300
304
313
318
322
327
336
341
346
351
360
365
370
376
386
391
396
402
413
418
424
429
441
446
452
458
470
476
482
488
501
507
514
520
From Dwg. D154557P01 Rev. 3
°
F)
13
14
195
198
211
215
229
232
247
251
267
271
287
291
309
313
331
336
355
360
381
386
407
413
435
441
464
470
495
501
527
533
88-A4HP5001-1D-EN