Mitsubishi Electric Mr. SLIM PLA-M100EA Installation Manual page 18

Hide thumbs Also See for Mr. SLIM PLA-M100EA:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
7. Test run
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
en
No sound
No sound
No sound
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
*1 If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2 If the beeper sounds 3 times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial 2 beeps to confirm the self-check start signal was received, the specified
refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
16
Wired remote
controller
Check code
P1
Intake sensor error
P2
Pipe (TH2) sensor error
P9
Pipe (TH5) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error/Float switch connector open
P5
Drain pump error
PA
Forced compressor error
P6
Freezing/Overheating protection operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
Pb
Indoor unit fan motor error
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
E0, E3
Remote controller transmission error
E1, E2
Remote controller control board error
– – – –
No corresponding
Wired remote
controller
Check code
E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
U2
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U1, Ud
Abnormal high pressure (63H worked)/Overheating protection operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan protection stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal synchro-
U9, UH
nous signal to main circuit/Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Symptom
Symptom
Remark
Remark
For details, check the LED
display of the outdoor controller
board.

Advertisement

Table of Contents
loading

Table of Contents