5-4. STANDARD OPERATION DATA
Representative matching
Mode
Capacity
Input
Indoor unit
Phase , Hz
Voltage
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature D.B. °C
Intake air temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1(MPa)=10.2(kgf/cm²)
OCH771C
PLA-ZM60EA2(-ET/-ER).UK
Cooling
W
6,100
kW
1.45
PLA-ZM60EA2(-ET/-ER).UK
1,50
V
230
A
0.22
PUZ-ZM60VHA2(-ET/-ER).UK PUZ-ZM71VHA2(-ET/-ER).UK
1,50
V
230
A
5.66
MPa
2.62
MPa
1.00
°C
79
°C
44
°C
15
m
7.5
D.B. °C
27
W.B. °C
19
13
D.B. °C
35
W.B. °C
24
0.73
0.13
PLA-ZM71EA2(-ET/-ER).UK
Heating
Cooling
7,000
7,100
1.71
1.65
PLA-ZM71EA2(-ET/-ER).UK
1,50
230
0.20
0.34
1,50
230
6.77
6.72
2.54
2.74
0.72
1.02
85
77
43
46
4
13
7.5
7.5
20
27
15
19
39
15
7
35
6
24
0.84
0.08
18
Heating
8,000
1.82
0.32
7.41
2.33
0.68
80
39
1
7.5
20
15
36
7
6