<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part 'A-Control Service Tool (PAC-SK52ST)' to connector
CNM on outdoor controller board.
[Display]
(1)Normal condition
Unit condition
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
(2)Abnormal condition
Indication
Outdoor controller
board
LED1 (Green) LED2 (Red)
1 blinking 2 blinking Connector (63H) is open.
2 blinking 1 blinking Miswiring of indoor/outdoor unit
connecting wire, excessive number
of indoor units (4 units or more)
Miswiring of indoor/outdoor unit
connecting wire (reversed wiring or
disconnection)
Startup time over
2 blinking Indoor/outdoor unit communication
error (signal receiving error) is
detected by in door unit.
Indoor/outdoor unit communication
error (transmitting error) is
detected by indoor unit.
Indoor/outdoor unit communication
error (signal receiving error) is
detected by outdoor unit.
Indoor/outdoor unit communication
error (transmitting error) is
detected by outdoor unit.
3 blinking Remote controller signal receiving error is
detected by remote controller.
Remote controller transmitting
error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting
error
is detected by indoor unit.
4 blinking
Abnormal if a connection of
indoor unit and outdoor unit
which uses different refrigerant
is detected.
Check code is not defined.
*1
Check code displayed on the remote controller
OCH774A
Outdoor controller board
LED1 (Green)
LED2 (Red)
Lit
Lit
Not lit
Lit
Not lit
Lit
Check
Contents
code
F5
E6
E7
E0
E3
E4
E5
EE
EF
PL
Check code
Lit
00, etc.
08, etc.
Lit
C5, etc.
Error
Inspection method
*1
1. Check if connector (63H) on the outdoor
controller board is not disconnected.
2. Check continuity of pressure switch (63H) by tester.
1. Check if indoor/outdoor connecting wire is
connected correctly.
2. Check if 4 or more indoor units are connected to
outdoor unit.
3. Check if noise entered into indoor/outdoor
connecting wire or power supply.
4. Re-check error by turning off power, and on
again.
1. Check if indoor/outdoor connecting wire is
connected correctly.
2. Check if noise entered into indoor/outdoor
connecting wire or power supply.
3. Check if noise entered into indoor/outdoor
controller board.
4. Re-check error by turning off power, and on
again.
1. Check if connecting wire of indoor unit or remote
controller is connected correctly.
2. Check if noise entered into transmission wire of
remote controller.
3. Re-check error by turning off power, and on
again.
Check if indoor/outdoor unit combination is authorized.
1. Check if remote controller is MA remote controller (PAR-21MAA)
2. Check if noise entered into transmission wire of remote controller.
3. Check if noise entered into indoor/outdoor connecting wire.
4. Re-check error by turning off power, and on again.
1. Check refrigerant pipes for disconnection or
leakage.
2. After the recovery of refrigerant, vacuum dry the
whole refrigerant circuit.
3. Refer to "9-5. HOW TO CHECK THE PARTS".
4. Check refrigerant circuit for operation.
64
A-Control Service Tool
Indication of the display
Alternately blinking display
Operation mode
Continued to the next page
Detailed
reference
page
P. 29
P. 30
(EA)
P. 30
(Eb)
P. 30
(EC)
P. 36
P. 36
P. 36
(E8)
P. 36
(E9)
P. 35
P. 36
P. 35
P. 36
P.37
P. 37
P. 38