DRYPOINT® RAX 600-5000 NA
At a flashing
LED: one or more alarms are active and the display shows
and the active alarms. When the
and the display shows
need to be reset.
The alarms are indicated by the following messages:
1.
: HPS pressure switch triggered (refrigerant high pressure) because the
condensation pressure is too high – see the corresponding paragraph (NOTE: press
the reset button on the HPS pressure switch when the problem is eliminated).
2.
: LPS pressure switch triggered (low pressure) because the refrigerant pressure is
too low – see the corresponding paragraph.
3.
: Con – The electrical protection of the compressor has triggered (see Q1/QC1
on the electric diagram) – reset and check the perfect functioning of the dryer.
4.
: Con – during first startup - The main electrical connection of the compressor
are connected incorrectly (see RPP on the electric diagram) – change the direction of
rotation and interchange two phases. These modifications must only be carried out by
a qualified electrician. DO NOT AVOID THE RPP PROTECTION: If the device is
operated with the incorrect direction of rotation, the compressor will fail immediately.
This will void the guarantee.
5.
: Con – one phase of power supply of dryer is missing (see RPP on the electric
diagram) – restore the missing phase.
6.
: Con – Reverse Phase Protector (RPP) is faulty – replace it.
7.
: Con – If installed – Thermal protection inside the compressor tripped (see MC1
on wiring diagram) – wait 30 minutes and try again.
8.
: FAn – The electrical protection of the fan has triggered (see QV1 on the electric
diagram) – reset and check the perfect functioning of the dryer (air-cooled).
9.
: FAn – The thermal protection in the fan has triggered (see MF on the circuit
diagram – wait 30 minutes and retry (air-cooled).
10.
: Hdt – The outlet temperature protection of the compressor has triggered as a
result of a very high temperature (probe T4) – see the corresponding paragraph.
11.
: ICE – The temperature inside the exchanger (probe T1) is too low – the dew
point is too low – see the corresponding paragraph.
12.
: LCP – The condensation pressure is too low – see the corresponding
paragraph.
13.
: PF4 – Failure temperature probe T4 (compressor outlet) – check the electric
cabling and/or replace the probe.
14.
: PFP – Failure pressure transducer BHP (condensation pressure) – check the
electric cabling and/or replace the transformer.
NOTE: The alarms need to be reset when the problem is eliminated (simultaneously press
reset
the
buttons for three seconds).
log
When the
LED flashes, one or more service warnings are active. When the
LED is lit: one or more service warnings need to be reset. The display shows the dew
point temperature and the service warning which is active or which is not yet reset.
The service warnings are indicated by the following messages:
1.
: PF1 – Failure temperature probe T1 (dew point) – check the electric cabling
and/or replace the probe.
2.
: PF2 – Failure temperature probe T2 (air IN) – check the electric cabling and/or
replace the probe.
3.
: PF3 – Failure temperature probe T3 (compressor intake) – check the electric
cabling and/or replace the probe.
4.
: Hdp – Dew point too high (higher than the adjusted alarm value) – see the
corresponding paragraph.
5.
: Ldp – Dew point too low – see the corresponding paragraph.
6.
: drn – The condensate drain does not work properly (condensate drain contact
open – if an electronic drain is installed) – see the corresponding paragraph.
7.
: SrV - Service – maintenance notification time expired (parameter SrV) – carry
out the scheduled maintenance and reset the hour meter.
8.
: dt – Compressor supply temperature too high
corresponding paragraph.
9.
: HCP – Condensation temperature too high – see the corresponding paragraph.
NOTE: The services need to be reset when the problem is eliminated (simultaneously
reset
press the
buttons for at least three seconds).
log
Maintenance, troubleshooting, spare parts and dismantling
LED is lit: one or more alarms need to be reset
and the alarms which are no longer active but which still
(probe T4) – see the