Appendix B - Sequence Of Operation - Carrier CRECOMZR101A00 Installation Instructions Manual

Vertical/horizontal low leak/ultra low leak economizerone accessory for small rooftop units select 3 to 12.5 tons
Table of Contents

Advertisement

Table B — Fixed Dry-Bulb without DCV (CO
THERMOSTAT
CONTROL MODE
Cooling
Heating
CONVENTIONAL
Cooling
Heating
Cooling
Heating
HEAT PUMP
Cooling
Heating
NOTE(S):
a. If Y2I is ON for more than a set time (15 minutes by default) and the OAT is greater than MAT setpoint (3MATSET), then Relay 2 energizes to allow Y2 pass-through to
enable Cooling Stage 2.
b. Configure 3STG3 DLY under Advanced Settings on page 27 to change to another set time.
APPENDIX B — SEQUENCE OF OPERATION EXAMPLES
OA GOOD TO
OCCUPIED
ECONOMIZE?
N/A
Yes
Yes
No
Yes
N/A
N/A
Yes
No
No
No
N/A
N/A
Yes
Yes
No
Yes
N/A
N/A
Yes
No
No
No
N/A
Sensor) — 2-Speed Fan
2
ECONOMIZER
Y1I
Y2I
Off
Off
On
Off
On
On, <15 mins
On
On, >15 mins
On
Off
On
On
Off
Off
Off
Off
On
Off
On
On, <15 mins
On
On, >15 mins
On
Off
On
On
Off
Off
Off
Off
On
Off
On
On, <15 mins
On
On, >15 mins
On
Off
On
On
Off
Off
On
Off
On
On
Off
Off
On
Off
On
On, <15 mins
On
On, >15 mins
On
Off
On
On
Off
Off
On
Off
On
On
31
DAMPER
Y1O
Y2O
POSITION
Off
Off
Min Pos L
Off
Off
Min Pos L to 100%
On
Off
Min Pos H to 100%
On
On/Off
,
Min Pos H to 100%
a
b
On
Off
Min Pos L
On
On
Min Pos H
Off
Off
Min Pos H
Off
Off
Closed
Off
Off
Closed to 100%
On
Off
Closed to 100%
On
On/Off
Closed to 100%
a,b
On
Off
Closed
On
On
Closed
Off
Off
Closed
Off
Off
Min Pos L
Off
Off
Min Pos L to 100%
On
Off
Min Pos H to 100%
On
On/Off
a,b
Min Pos H to 100%
On
Off
Min Pos L
On
On
Min Pos H
Off
Off
Min Pos H
On
Off
Min Pos H
On
On
Min Pos H
Off
Off
Closed
Off
Off
Closed to 100%
On
Off
Closed to 100%
On
On/Off
a,b
Closed to 100%
On
Off
Closed
On
On
Closed
Off
Off
Closed
On
Off
Closed
On
On
Closed