Examples of connection diagrams for universal inputs/outputs
Digital inputs
Count inputs:
Analog inputs
Analog outputs
Siemens Schweiz AG
Smart Infrastructure
Ux
Ux
Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in
the same cable duct, must be shielded.
M
B
Ux
Ux
Ux
V +
V
Ux
Ux
+
V+
Ux
Ux
V V + +
V V + +
Ux
Ux
Ux
S1
Feedback contact (NO)
S2
Feedback contact (NC)
B1
Temperature sensor LG-Ni 1000
B2
Temperature sensor, general
B3
Resistance transmitter
B4
Active sensor with 0...10 V output powered by the
+
automation station
B5
Active sensor with 0...10 V output with external
power
V +
Do NOT ground external power (ground loops)
B6
Active sensors 0 ... 20 mA or 4 ... 20 mA (2-wire)
On U1, U2, U7, U8 only
Y1
Device with input DC 0...10 V
Y2
General device with control input DC 0...10 V
powered by the automation station
Y3
General device with control input DC 0...10 V
Do NOT ground external power (ground loops)
V +
17
A6V11937668_en--_l
2023-12-22