Outputs
12 universal inputs / outputs U1...U12 with the following output functions (10-bit DA
converter):
Voltage output, analog
Type
AO 0-10 V
AO 0-10 V
standard
Relay output (outputs DO1...DO4)
External supply line fusing
Non-renewable fuse
Circuit breakers
Switching voltage AC/DC
Current load AC
Current on make AC
Current load DC
Response / release time
Contact life at AC 250 V (reference values)
At 0.3 A resistive
NO contact at 3 A resistive
NC contact at 2 A resistive
Reduction factor for inductive load (cos phi = 0.6)
Insulating strength between relay contacts and system
electronics (reinforced insulation).
No overvoltage protection is used when switching inductive loads
Risk of heavy electromagnetic disturbances and lower contact life when no overvoltage
protection is used when switching inductive loads.
Siemens Schweiz AG
Smart Infrastructure
Range (over range)
0...10 V (-0.05...10.6 V)
0...100%
0% = 0 V, 100% = 10 V
(-0.05...10.6 V)
When switching inductive loads (e.g. contactors or electric motors) it is strongly
recommended to use suitable overvoltage protection devices to avoid heavy
electromagnetic disturbances and to ensure the specified contact life.
Resolution
1 mV
0.01 %
Max. 10 A, slow
Max. 13 A, characteristic B, C, D as per EN 60898
Max. AC 250 V / DC 30 V
Min. AC/DC 12 V
NO contact: Max. 4 A resistive, 3 A inductive (cos phi
0.6)
NC contact: max. 2 A resistive, 1.5 A inductive (cos phi
0.6)
Min. 1 mA at AC 250 V
Min. 10 mA at AC 12 V
NO contact: Max. 10 A (1 s)
NC contact: Max. 3 A (1 s)
NO contact: Max. 3 A resistive at DC 30 V
NC contact: Max. 1 A resistive at DC 30 V
Min. 10 mA resistive at DC 12 V
7 ms / 3 ms typical
5
5 x 10
switching cycles
5
1 x 10
switching cycles
5
1 x 10
switching cycles
0.6
AC 3750 V, as per EN 60730-1
CAUTION
Output current
Max. 1 mA
Max. 1 mA
13