Perform the following storage procedure before taking a generator set out of service for three months or longer. Follow the
engine manufacturer's recommendations, if available, for fuel system and internal engine component storage.
WARNING
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or
equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down
the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (–) lead
first. Reconnect the negative (–) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the
generator set by the remote start/stop switch.
WARNING
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and
exhaust system components become extremely hot during operation.
DANGER
Servicing the generator set when it is operating. Exposed moving parts will cause severe injury or death. Keep hands,
feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens,
and covers before operating the generator set.

10.1 Lubrication System

Prepare the engine lubricating system for storage as follows.
Note:
Kohler recommends the use of Kohler genuine oil and filters.
1.
Run the generator set for a minimum of 30 minutes to bring it to normal operating temperature.
2.
Stop the generator set.
3.
With the engine still warm, drain the oil from the crankcase.
4.
Remove and replace the oil filter.
5.
Refill the crankcase with oil suited to the climate.
6.
Run the generator set for two minutes to distribute the clean oil.
7.
Stop the generator set.
8.
Check the oil level and adjust, if needed.
TP-7173
10/20
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the
negative (–) lead first when disconnecting the battery. Reconnect the negative (–)
lead last when reconnecting the battery.
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until it cools.
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
Section 10.

Storage Procedure

41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kg80rKg100Kg125Kg125rKg150Kg150r ... Show all

Table of Contents