Identify the hot aisle and cold aisle layout at the installation site, and make sure ambient air
flows into the switch from the cold aisle and exhausts to the hot aisle.
Identify the airflow designs of neighboring devices, and prevent hot air flowing out of the
neighboring devices from entering the top device.
The rack is sturdy enough to support the switch and its accessories.
The rack is reliably grounded.
To ensure correct operation and long service life of your switch, install it in an environment that meets
the requirements described in the following subsections.

Temperature/humidity

Maintain the temperature and humidity in the equipment room in the acceptable ranges.
Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical
property change of materials, and metal corrosion.
Lasting low relative humidity can cause washer contraction and ESD and cause problems
including loose mounting screws and circuit failure.
High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the switch.
For information about the temperature and humidity requirements, see H3C S9825 & S9855 Switch
Series Hardware Information and Specifications.

Cleanliness

Dust buildup on the chassis might cause electrostatic adsorption and dust corrosion, resulting in
poor contact of metal connectors and contact points. This might shorten the device's lifetime and
even cause device failure in the worst case.
cleanliness.
Table1-1 Switch requirement for cleanliness
Substance
Dust particles

Corrosive gas limit

Corrosive gases can accelerate corrosion and aging of metal components. Make sure the corrosive
gases do not exceed the concentration limits as shown in Table1-2.
Table1-2 Corrosive gas concentration limits
Gas
SO
2
H
S
2
Cl
2
HCI
HF
NH
3
O
3
Particle diameter
≥ 0.5 µm
Average concentration (mg/m
0.3
0.1
0.1
0.1
0.01
1.0
0.05
2
Table1-1
describes the switch requirement for
Concentration limit
≤ 1.8 × 10
3
)
Maximum concentration (mg/m
1.0
0.5
0.3
0.5
0.03
3.0
0.1
7
3
particles/m
3
)