Daikin RXM20R Service Manual page 65

Hide thumbs Also See for RXM20R:
Table of Contents

Advertisement

RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02
Prerequisite: Recuperate the refrigerant from the refrigerant circuit, see
"5.2.2 Repair
procedures" [
1 If needed, remove any parts to create more space for the removal of the
compressor.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
A
A Class 20~35 unit
a Compressor wire terminals cover
A
A Class 42~71 unit
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
4
 212].
a
a
4
Components
|
Service manual
65