Automatic restart after instantaneous power failure (Pr. 57, Pr. 58, Pr. 162 to Pr. 165)

Pr. 57 "coasting time for automatic restart after instantaneous power
failure/commercial power supply-inverter switch-over"
Pr. 58 "cushion time for automatic restart after instantaneous power
failure/commercial power supply-inverter switch-over"
Pr.162 "Automatic restart after instantaneous power failure selection"
Pr.163 "First cushion time for restart"
Pr.164 "First cushion voltage for restart"
Pr.165 "Restart stall prevention operation level"
You can restart the inverter without stopping the motor (with the motor coasting) when the commercial
z
power supply is switched to the inverter operation or when the power is restored after an instantaneous
power failure. (When automatic restart operation is set to be enabled, UVT and IPF among the alarm
output signals will not be output at occurrence of an instantaneous power failure.)
Parameter
Factory Setting
Number
57
58
162
163
164
165
150%
Voltage
Pr.164
(Pr.163)
Setting Range
9999
0, 0.1 to 5 s, 9999
1.0 s
0 to 60 s
0
0, 1
0 s
0 to 20 s
0%
0 to 100%
0 to 200%
Pr.58
Time
Voltage rise time
Remarks
9999: No restart
0: Frequency search, 1: No frequency
search
NFB
MC1
R 〈L
1
S 〈L
2
T 〈L
3
R1 〈L
11
S1 〈L
21
STF
CS
SD
CS
SD
85
PARAMETERS
MC2
×
MC3
U
V
IM
W
MC switching sequence
Connect CS-SD for use of only
automatic restart after instantaneous
power failure.