<Error code List>
The corresponding error code in the following list is displayed if an error is detected in any communication
request data form the computer.
Error
Item
Code
H0
Computer NAK error
H1
Parity error
H2
Sum check error
H3
Protocol error
H4
Framing error
H5
Overrun error

H6
H7
Character error

H8

H9
HA
Mode error
Instruction
HB
error
HC
Data range error

HD

HE

HF
The number of errors consecutively detected in communication
request data from the computer is greater than allowed number
of retry times.
The parity check result does not match the specified parity.
The sum check code in the computer does not match that of the
data received by the inverter.
Data received by the inverter is in the wrong protocol, data
receive is not completed within the given time, or CR and LF are
not as set in the parameter.
The stop bit length is not as specified.
New data has been sent by the computer before the inverter
completes receiving the preceding data.
The character received is invalid (other than 0 to 9, A to F,
control code).
Parameter write was attempted in other than the computer link
operation mode or during inverter operation.
code
The specified command does not exist.
Invalid data has been specified for parameter write, frequency
setting, etc.
Definition






122
PARAMETERS
Inverter Operation
Brought to an alarm stop
(E.OPT) if error occurs
continuously more than
the allowable number of
retry times.

Does not accept receive
data but is not brought to
alarm stop.


Does
not
accept
receive data but is not
brought to alarm stop.



or