Mitsubishi Electric FR-A520-0.4K-NA Instruction Manual page 63

Transistorized inverter
Hide thumbs Also See for FR-A520-0.4K-NA:
Table of Contents

Advertisement

( 3 ) Parameter setting check
We recommend the following parameters to be set by the user.
Set them according to the operation specifications, load, etc. (Refer to page 57.)
Parameter
Number
1
Maximum frequency
2
Minimum frequency
7
Acceleration time
8
Deceleration time
Second acceleration/deceleration
44
time
45
Second deceleration time
Third acceleration/deceleration
110
time
111
Third deceleration time
9
Electronic thermal O/L relay
14
Load pattern selection
71
Applied motor
73
0-5V/0-10V selection
900
FM terminal calibration
901
AM terminal calibration
902
Frequency setting voltage bias
903
Frequency setting voltage gain
904
Frequency setting current bias
905
Frequency setting current gain
Name
Used to set the maximum and minimum output frequencies.
Used to set the acceleration and deceleration times.
Used to set the current of the electronic overcurrent protection to protect
the motor from overheat.
Used to select the optimum output characteristics which match the
application and load characteristics.
Used to set the thermal characteristics of the electronic overcurrent
protection according to the motor used.
Used to select the specifications of the frequency setting signal entered
across terminal 2-5 to perform operation with the voltage input signal.
Used to calibrate the meters connected across terminals FM-SD and AM-5.
Used to set the magnitude (slope) of the output frequency relative to the
frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mA DC) as desired.
Application
52
OPERATION

Advertisement

Table of Contents
loading

Table of Contents