Intermatic AG3000G Installation Instructions

1 or type 2 surge protection device

Advertisement

Quick Links

IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
Risk of Fire or Electric Shock
WARNING
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Intended for indoor or outdoor use.
• Installation and/or wiring must be in accordance with national and local electrical code(s).
• Installation and service to be performed by a qualified licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 20,000 rms symmetrical amperes.
• This unit contains no serviceable parts.
AVERTISSEMENT
• L'installation et/ou le câblage doivent être conformes aux exigences du code de l'électricité local en vigueur et/ou du Code canadien de l'électricité.
• L'installation et l'entretien doivent être effectués par un technicien ou électricien qualifié.
• Convient à un circuit capable de fournir PAS plus de 20 000 A efficaces symétriques.
• Cet appareil ne contient aucune pièce réparable.
NOTICE
NOTICE
• Thoroughly read instructions before installing SPD Unit.
• This product does not protect against lightning strikes.
• If the unit is mounted outdoors, the threaded nipple must be mounted horizontally into a suitable enclosure.
Type 1 installation:
A typical installation of a type 1 SPD will be connected between the
secondary of the service transformer and the line side of the service
panel. This installation is intended to be installed without overcurrent
protection to the SPD.
1. Determining location:
• Ensure conductor lengths are as short and straight as
possible for best performance. Do not coil excess wire. The
SPD functions best if all bends in wires are rounded, ideally
to a 4" radius. Hard 90 degree bend will reduce efficiency.
Cut all leads to the correct length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be
mounted outside.
2. Ensure all mounting and connections are correct and secure.
Once energized the green indicator LED will be ON and visible
through the cover of the SPD.
Type 2 installation:
A typical installation of a type 2 SPD will be connected to the load side
of the service panel and is intended to be installed with overcurrent
protection to the SPD.
1. Determining location:
• Ensure conductor lengths are as short and straight as
possible for best performance. Do not coil excess wire. The
SPD functions best if all bends in wires are rounded, ideally
to a 4" radius. Hard 90 degree bend will reduce efficiency.
Cut all leads to the correct length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be
mounted outside.
2. Connect the white wire from the SPD to the neutral bus bar in
the panel as shown.
• Connection may also be made to the neutral/ground bus bar
if panel does not have a separate ground bus bar.
3. Connect the two black wires to a circuit breaker as shown.
For best performance from SPD the maximum recommended
circuit breaker size of 240 VAC,up to 30 A, 2-pole should be
used.
4. Ensure all mounting and electrical connections are correct and
securely fastened. Once energized the green indicator LED will
be ON and visible through the cover of the SPD.
AC Disconnect Installation
1. To be installed with over current protection up to 60 A.
Maintenance:
AC Voltage SPD:
• Periodically check SPD to ensure green indicator LED is ON.
If green LED is OFF, protection has diminished and the SPD
should be replaced immediately.
Model AG3000/AG3000G
Type 1 or Type 2 Surge Protection Device (SPD)
Risque d'incendie ou de choc électrique
INSTALLATION INSTRUCTIONS
Type 2 Installation
Line
120 V
Neutral
0 V
Ground
120 VAC Two wire single phase with
separate ground.
Found at connections for individual
pieces of equipment such as pumps,
single phase motors and HVAC applications.
NOTE: Both Black wires connect to Line.
Neut/
Grounded
Line
Conductor
Line
White or Green
Line
Line
AC Disconnect
Load
Load
Main Breaker
2-Pole, 20 A circuit
breaker shown
A=Black (Line)
B=Black (Line)
C=Neutral/Grounded
(White or Green)
Line
Line
(BLACK)
(BLACK)
120 V
Neutral/
Grounded
(WHITE or GREEN)
AG3000/
AG3000G
Black
Black
Typical 120/240 VAC Application
According to NEC Article 285.27
For applications where the neutral wire is not present, the
SPD white wire (grounded conductor) may be identified
with green tape for connection to the equipment ground.

Advertisement

loading

Summary of Contents for Intermatic AG3000G

  • Page 1 INSTALLATION INSTRUCTIONS Model AG3000/AG3000G Type 1 or Type 2 Surge Protection Device (SPD) IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS Risk of Fire or Electric Shock WARNING • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
  • Page 2 A green LED indicator will illuminate when the AG3000/AG3000G is operating normally and protecting your equipment. If the green indicator light is OFF, the AG3000/AG3000G will need to be replaced. You can order a new unit and have it installed by your local service installer. It is the owner’s responsibility to check the green light status indicator of the AG3000/AG3000G.
  • Page 3 (2) What is Not Covered By This Warranty Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the Product, (b) damage caused by use of the Product for...
  • Page 4 INTERMATIC INCORPORATED LIBERTYVILLE, ILLINOIS 60048 http://www.intermatic.com 158--02633...