Maximum Liquefied Propane Delivery Capacity
In Thousands of BTU/H (0.5 in WC Pressure Drop)
Length (including fittings)
Pipe Size
10 ft
20 ft
(3 m)
(6 m)
1
/
in
291
200
2
3
/
in
608
418
4
1 in
1,150
787
1
1
/
in
2,350
1,620
4
1
1
/
in
3,520
2,420
2
2 in
6,790
4,660
3.3.2 Measuring the Inlet Gas Pressure
WARNING
The water heater cannot function properly without sufficient inlet gas pressure. Measuring the inlet gas pressure should be performed by
a licensed professional only.
The inlet gas pressure must be maintained between 3.5 in and 10.5 in WC for natural gas and between 8.0 in and 13 in WC for liquefied
propane.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of
that system at test pressures in excess of
individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
(3.5 kPa).
If gas pressure is out of the acceptable range or an excessive pressure drop is observed, contact the gas supplier or a qualified
Note
installer to supply proper gas pressure to the unit.
To measure the inlet gas pressure:
1. Shut off the manual gas valve on the gas supply line.
22
Installing the Water Heater
30 ft
40 ft
50 ft
60 ft
(9 m)
(12 m)
(15 m)
(18 m)
160
137
122
110
336
287
255
231
632
541
480
434
1,300
1,110
985
892
1,940
1,660
1,480
1,340
3,750
3,210
2,840
2,570
1
/
psi (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its
2
Gas Valve
80 ft
100 ft
125 ft
(24 m)
(30 m)
(38 m)
101
94
89
212
197
185
400
372
349
821
763
716
1,230
1,140
1,070
2,370
2,200
2,070
Opened
Closed
150 ft
175 ft
200 ft
250 ft
(45 m)
(53 m)
(60 m)
(76 m)
84
74
67
62
175
155
140
129
330
292
265
243
677
600
543
500
1,010
899
814
749
1,950
1,730
1,570
1,440
1
/
2
psi

Hide quick links: