Omron NXR-ILM08C-ECT Manual page 12

Environment-resistive remote terminal nxr-series io-link master unit for ethercat
Hide thumbs Also See for NXR-ILM08C-ECT:
Table of Contents

Advertisement

NXR-ILM08C-ECT
Digital outputs for pin 4 or
digital outputs for pin 2
(in SIO (DO) Mode)
Current consumption
Weight
Dimensions
Isolation method
Circuit layout
*1. Used as a power supply for IO-Link devices or non-IO-Link input devices. Supplies power from the Unit/input power supply of the IO-Link
Master Unit to external devices through I/O connectors.
*2. Detects a short-circuit that occurred between pin 1 and pin 3 to protect the IO-Link Master Unit.
*3. Detects a short-circuit that occurred between pin 2 and pin 3 and between pin 4 and pin 3 to protect the IO-Link Master Unit.
12
Item
Power supply used
Internal I/O common
Output type
Rated voltage
Maximum load current
Leakage current
Residual voltage
ON/OFF response time
Short-circuit protection
Short-circuit detection
Unit/input power supply
Output power supply
Output power supply
PNP
Open-drain
24 VDC (20.4 to 26.4 VDC)
2 A/pin
0.1 mA max.
1.5 V max.
1.0 ms max.
Provided *3
Provided *3
60 mA
100 mA
440 g
240 × 24.2 × 62 mm (W × H × D)
(The height is 38 mm when the connectors are included.)
No isolation
EtherCAT communications
connector (input)
EtherCAT communications
connector (output)
U/IN P+
U/IN P-
Power supply
connector (input)
(PWR IN)
OUT P+
OUT P-
U/IN P+
U/IN P-
Power supply
connector (output)
(PWR OUT)
OUT P+
OUT P-
Specification
Internal
L+(Pin1)
circuits
C/Q(Pin4)
I/Q(Pin2)
IO-Link
L-(Pin3)
circuits/
Non-isolated
power supply
input
L+(Pin1)
circuits
circuits
C/Q(Pin4)
I/Q(Pin2)
L-(Pin3)
Output
circuits
I/O
connector
P1
I/O
connector
P8