Lennox LHT Series Service Manual page 30

Hide thumbs Also See for LHT Series:
Table of Contents

Advertisement

TABLE 6
156 Compressor 1 Frequency 56Hz - 581167-01
Outdoor
Circuit 1
Coil En-
tering Air
Temp⁰F
Dis. +10
Suc. +5
psig
65
218
75
262
85
305
95
350
105
400
110
454
TABLE 7
180 Compressor 1 Frequency 56Hz - 581168-01
Outdoor
Circuit 1
Coil En-
tering Air
Temp⁰F
Dis. +10
Suc. +5
psig
65
243
75
280
85
321
95
366
105
415
110
469
Circuit 2
Dis. +10
Suc. +5
psig
psig
psig
110
232
118
129
279
138
146
319
144
149
365
148
152
416
150
155
471
153
Circuit 2
Dis. +10
Suc. +5
psig
psig
psig
133
248
132
137
286
135
141
328
138
144
374
140
146
424
143
149
477
146
240 Compressor 1 Frequency 68Hz - 581169-01
Outdoor
Coil En-
tering Air
Temp⁰F
Dis. +10
psig
65
260
75
297
85
338
95
384
105
434
110
485
B-Charge Verification - Approach Method - AHRI
Testing (Fin/Tube Coil)
1 - 1- Using the same thermometer, compare liquid
temperature to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at
outdoor coil outlet) minus ambient temperature.
2 - Approach temperature should match values in table
9. An approach temperature greater than value
shown indicates an undercharge. An approach
temperature less than value shown indicates an
overcharge.
3 - The approach method is not valid for grossly over or
undercharged systems. Use tables 6, 7 and 8 as a
guide for typical operating pressures.
APPROACH TEMPERATURES - FIN/TUBE COIL
Unit
156
5°F + 1 (2.8°C +0.5) 4.0°F + 1 (2.2°C +0.5)
180
2°F + 1 (1.1°C +0.5) 5.0°F + 1 (2.8°C +0.5)
240
6°F + 1 (3.3°C +0.5)
Page 30
TABLE 8
Circuit 1
Circuit 2
Suc. +5
Dis. +10
psig
psig
135
264
136
304
138
346
140
394
142
443
144
494
TABLE 9
Liquid Temp. Minus Ambient Temp.
1st Stage
2nd Stage
6°F + 1 (3.3°C +0.5)
Suc. +5
psig
135
136
138
140
142
144