Fan
Check to make sure that no dust has accumulated inside the fan or
on its blades, as this condition will cause a reduction in the air flow
rate and provoke polluting combustion.
Burner
Clean the outside of the burner.
Clean and grease the cam variable profile.
Boiler
Clean the boiler as indicated in its accompanying instructions in or-
der to maintain all the original combustion characteristics intact, es-
pecially the flue gas temperature and combustion chamber
pressure.
LIGHT OIL OPERATION
Pump
Delivery pressure must correspond with the Fig. 17.
The depression must be less than 0.45 bar
Unusual noise must not be evident during pump operation
If the pressure is found to be unstable or if the pump runs noisily,
the flexible hose must be detached from the line filter and the fuel
must be sucked from a tank located near the burner. This measure
permits the cause of the anomaly to be traced to either the suction
line or the pump.
If the problem lies in the suction line, check to make sure that the
filter is clean and that air is not entering the piping.
Filters
Check the filtering baskets on line and at nozzle present in the sys-
tem. Clean or replace if necessary.
If rust or other impurities are observed inside the pump, use a sep-
arate pump to lift any water and other impurities that may have de-
posited on the bottom of the tank.
Nozzles
It is advisable to replace nozzles every year during regular main-
tenance operations.
Do not clean the nozzle openings; do not even open them.
Flexible hoses
Check to make sure that the flexible hoses are still in good condi-
tion.
Fuel tank
Approximately every 5 years, or whenever necessary, suck any
water or other impurities present on the bottom of the tank using a
separate pump.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do not
correspond to a proper combustion, contact the Technical Assist-
ant and have him carry out the necessary adjustments.
Maintenance
Gas leaks
Make sure that there are no gas leaks on the pipework between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do not
correspond to a proper combustion, contact the Technical Assist-
ant and have him carry out the necessary adjustments.
.
.