Section 2: Installation
January 2013
2.6.6

Wiring procedure

The signal terminals are located in a compartment of the electronics housing separate from the
flowmeter electronics. Connections for a HART-based communicator and a current test
connection are above the signal terminals.
limitations for the flowmeter.
Note
A power disconnect is required to remove power from the transmitter for maintenance,
removal, and replacement.
Power supply
Power Supply Specifications:
Typical installations use a 22 Vdc – 28 Vdc power supply. The dc power supply should provide
clean power with less than 2% ripple. Refer to
Loop resistance specification:
If HART communication is required, a minimum resistance of 250 dc is required between the
power supply and the transmitter. *Note: See the loop load calculation section to determine the
maximum allowable loop resistance as a function of power supply voltage.
Typical single loop wiring diagram:
*Loop Load Calculation: R
Where:
16
V
ps
= (V
loop(max)
R
= 250 . Required for HART communication.
loop(min)
R
= The maximum value the loop load resistor can be.
loop(max)
V
= Power Supply Voltage
ps
10.8 = minimum terminal voltage "V
0.024 = maximum transmitter current in Adc
Get other manuals https://www.bkmanuals.com
Figure 2-10
illustrates the power supply load
Figure 2-10
as a quick reference.
V
8600
terminals
R
loop
– 10.8) / 0.024
ps
" in Vdc.
terminals
Reference Manual
00809-0100-4860, Rev BC