The protection can be improved by installing a larger supply transformer and/or bigger cables, and in
most cases by selecting aR fuses instead of gG fuses. Selection of smaller fuses improves the
protection, but it can affect the fuse life time and lead to unnecessary operation of the fuses.
In case of any uncertainty regarding the drive protection, please contact your local ABB.

Cable types

The table below gives copper and aluminum cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN/IEC 60204-1 and
IEC 60364-5-52:2001). For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
Copper cables with concentric
56
71
88
107
137
167
193
223
255
301
274
334
386
446
510
602
579
669
765
903
copper shield
Max. load
Cable type
current
A
2
mm
3×16
3×25
3×35
3×50
3×70
3×95
3×120
3×150
3×185
3×240
2 × (3×70)
2 × (3×95)
2 × (3×120)
2 × (3×150)
2 × (3x185)
2 × (3×240)
3 × (3×120)
3 × (3×150)
3 × (3×185)
3 × (3×240)
Aluminum cables with concentric
copper shield
Max. load
Cable type
current
A
mm
69
3×35
83
3×50
107
3×70
130
3×95
151
3×120
174
3×150
199
3×185
235
3×240
214
2 × (3×70)
260
2 × (3×95)
302
2 × (3×120)
348
2 × (3×150)
398
2 × (3×185)
470
2 × (3×240)
522
3 × (3×150)
597
3 × (3×185)
705
3 × (3×240)
3BFA 01051905 C