Honeywell SmartValve SV9401 Installation Instructions Manual page 5

Table of Contents

Advertisement

SV9401/SV9402/SV9403, SV9501/SV9502/SV9503, SV9601/SV9602 SMARTVALVE™
PRESSURE
REGULATOR
CAP
Fig. 1. Convertible Regulator for SmartValves.
3. Make sure that the O-ring fits in the groove of the
flange. If the O-ring is not attached or missing, do
not use the flange.
4. With the O-ring facing the ignition system control,
align the screw holes on the ignition system control
with the holes in the flange. Insert and tighten the
screws provided with the flange. See Fig. 2. Tighten
the screws to 25 inch-pounds of torque to provide a
gas-tight seal.
VALVE OUTLET
9/64 INCH HEX SCREWS (4)
1
DO NOT USE FLANGES ON 3/4 IN. INLET AND 3/4 IN. OUTLET
MODELS, AND ON THE 3/4 IN. OUTLET SIDE OF 1/2 IN. INLET
AND 3/4 IN. OUTLET MODELS.
Fig. 2. Firmly fasten flange to valve but do not over-
tighten screws.
Bushings
1. Remove the seal over the ignition system control
inlet or outlet.
2. Apply a moderate amount of good quality pipe
compound to the bushing, leaving two end threads
bare. On an LP installation, use compound resistant
to LP gas. Do not use Teflon tape.
3. Insert the bushing in the ignition system control and
carefully thread the pipe into the bushing until tight.
Follow the instructions below to installing the piping, and
control. Connect the pilot tubing and wiring. Make sure the
leak test you perform on the control after completing the
installation includes the adapters and screws. If you use a
wrench on the valve after the flanges are installed, use the
wrench only on the flange, not on the control. See Fig. 6.
OR
OTHER SIDE
OF CAP
M11678
1
FLANGE
Location
The SV9401/SV9402/SV9403, SV9501/SV9502/SV9503,
and SV9601/SV9602 are mounted in the
appliance vestibule on the gas manifold.
IMPORTANT
Make sure the mounting location protects the
control from dripping water and excessive
humidity.
IMPORTANT
Make sure the mounting location maximum and
minimum ambient temperature are both within
the specified acceptable range.
Install Piping on Control
All piping must comply with local codes and ordinances or
with the National Fuel Gas Code (ANSI Z223.1 NFPA No.
54), as applicable.
1. Use new, properly reamed pipe free from chips. If
tubing is used, make sure the ends are square,
deburred and clean. All tubing bends must be
smooth and without deformation.
2. Run pipe or tubing to the ignition system control. If
tubing is used, obtain a tube-to-pipe coupling to
connect the tubing to the ignition system control.
3. Install a sediment trap in the supply line to the
ignition system control as shown in Fig. 3.
DROP
HORIZONTAL
3 IN.
(76 MM)
MINIMUM
HORIZONTAL
1
M7927C
RISER
3 IN.
(76 MM)
MINIMUM
CAUTION
GAS LEAKAGE HAZARD
FAILURE TO FOLLOW PRECAUTIONS CAN
RESULT IN A GAS-FILLED WORK AREA.
SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP.
TEST FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
1
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
Fig. 3. Sediment trap installation.
5
PIPED
GAS
SUPPLY
IGNITION
SYSTEM
CONTROL
DROP
TUBING
GAS
SUPPLY
IGNITION
SYSTEM
CONTROL
IGNITION
SYSTEM
CONTROL
RISER
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
M3343B
69-1004—2

Advertisement

Table of Contents
loading

Table of Contents