Wine cellar cooling system self-contained (14 pages)
Summary of Contents for Thenow HSN-J15-Z
Page 1
Shanghai Thenow Purification Technology Co.Ltd Wine Cellar Cooling Units Self-contained User Manual Thank you for purchasing this “Thenow”product; Please read this manual carefully before attempting to install, operate or service; Please retain this booklet for future reference.
Page 2
!!! WARNING !!! To avoid the risk of electrical shock, property damage, personal injure or death, please read the following instructions carefully with safety or warning labels. *During transportation or moving, please follow the correct direction on the packing case. After transportation or moved, it needs to be allowed to stand for more than 24 hours before it can be turned on.
Wine Cellar Cooling Units Through-the-Wall Thenow through-the-wall wine cellar cooling unit is specially designed to match the demands in foreign markets, It is a ductless wine cellar cooling units with evaporator and condenser are housed together in one unit. it offers a compact design that can be applied to the unique today’s do-it-yourself modern wine cellar or wine wall.
Dimensions & Technical Data Dimensions HSN-JT20: 5...
Page 6
Technical Data Model Unit JT20 Semi Buried m³ 4~7 Cellar Size Insulated* m³ 4~12 Power V/HZ 220V/50Hz Cooling 0.72 Heating Air Flow Static Pressure Noise dB(A) Refrigerant R290 Control PC Full-touch smart control Temperature 10-18℃, ±2℃ ℃ Humidity 50~70%, ±5% ℃...
Installation and Debugging Pre Installation Inspection A. Check the outer packing for breakage. B. Machine model (nameplate), check whether it is consistent with what you ordered. C. The appearance of the whole machine is intact. D. Sit unit upright for at least 24 hours before installation. Check the Packing Details : Item No.
Page 8
Installation Disconnect electric power from the appliance before performing any maintenance or repairs,failure to do so could result in death or electrical shock. Because of potential safety hazards under a certain condition, we strongly recommend against the use of an extension cord.
Page 9
5. To avoid any air leakage, before install the unit, foam tape needs to be placed in the bottom and side of the unit. 6. Working environment: Temperature 5℃-35℃,Humidity RH<80% 7. Recommend air duct: A- Heat-insulating phenolic board, thickness 15~20mm B- Stainless steel duct, 20mm insulation 8.
Page 10
Make sure the installation position of the unit on the wall, and the distance from the top of the unit to the ceiling shall not be less than 100mm. Mark hole location for the unit,outline a rectangle 412mm(width) by 391mm(height) where the unit will be placed into the wall.
Page 11
Otherwise, the water will always be supplied to the machine in a normally open state, which will cause the equipment to leak and fail to operate. Below suggested water flow rate of Thenow self-contained cooling units for your checking: ( Unit: L/M) Model...
Page 12
Common Mounting Methods: HSN-JT20 I: Through-the-wall 12...
Page 14
Online Debugging 1. Preparation work before starting the unit a. Confirm that the power supply of the user distribution box is single-phase 220V, the fluctuation range does not exceed 10%, and the capacity of the distribution box meets the unit use requirements; b.
operation, choosing it running at high speed or low speed freely. 4.) Running the unit. Check unit to confirm the compressor is running, such as the hum of the compressor or cool air leaving the unit. Check for any unusual noise or vibration, such as clanking or rubbing. After the machine runs for 30 minutes or several hours, up to a day or more: 1.
Page 16
Technical Specifications PCB:AC220V±10% 50/60HZ Power Supply Display:DC12V Shall Material Flame retardant ABS+PC Power <12W Pich of Installation 60mm PCB:123mm×85mm Size Display:91mm×90mm Storage Environment -10~~70℃ 5%~~95%RH -10~~70℃ 5%~~95%RH Working Condition 1. Remove the plastic frame and screw from the packaging box,and then install and fix the plastic frame to the 86 mounting box inside the wall after the wire is threaded out of the plastic frame.
Page 17
10.Cellar temperature 11.Cellar humidity Note: Because all Thenow Cooling Units are using same displayer now, for the single cooling unit like JC8, some functions indicating above are not available. Very regretful for the troubles may bringing to you. Touch the switch icon in the lower...
Touch icon 'Mode' to choose the Mode running mode, default value is 'Auto' Touch icon next to the switch, choosing the running mode of the fan at 'A' or 'M' Fan Running Mode (A-Auto running speed, M-Selecting running speed manually) Set the fan speed (Only available at the Touch the fan icon to change the...
Page 19
should be cleaned at least once every six months under the running environment of the wine cellar. The cleaning steps are as follows: a. Please unplug the power supply without taking out the unit, as shown in the figure below, first remove the air filter cover shown in number 4 in the figure.
Troubleshooting WARNING Disconnect electric power from the appliance before performing any maintenance or repairs,failure to do so could result in death or electrical shock. If maintenance is needed, wait for 3 minutes after power failure (let capacitor discharge on PCB), and then open the maintenance door.
1. Check machine mode or check room 1. The machine model choice Unit running too tightness. improper or improper room sealing. long or continually 2. Check installation location increase 2. Ambient temperature to high. setting. 1. Evaporator airflow restricted. 1. Check the fan. 2.