GENERAL DESCRIPTION
The CTVUE-308A Operator Interface Terminal combines unique capabilities
normally expected from high-end units with a very affordable price. It is built
around a high performance core with integrated functionality.
The 308 is able to communicate with many different types of hardware using
high-speed RS232/422/485 communications ports and Ethernet 10 Base T/100
Base-TX communications. In addition, the 308 features USB for fast downloads
of configuration files and access to trending and data logging. A CompactFlash
socket is provided so that Flash cards can be used to collect your trending and
data logging information as well as to store larger configuration files.
In addition to accessing and controlling of external resources, the 308 allows
a user to easily view and enter information. Users can enter data through the
touchscreen or front panel 7-button keypad.
ORDERING INFORMATION
DESCRIPTION
Operator Interface with TFT display for indoor
applications, textured finish with embossed keys
CANopen Optional Communications Card
DeviceNet option card for operator interfaces with
isolated high speed communications ports
RS 232/485 Optional Communication Card
Profibus DP Optional Communication Card
CTVUE Programming Software CD
RS-232 Programming Cable
USB Cable
VGA DISPLAY AND TOUCHSCREEN
CONFIGURED USING CTVue CONFIGURATOR SOFTWARE
UP TO 5 RS-232/422/485 COMMUNICATIONS PORTS
(2 RS-232 AND 1 RS-422/485 ON BOARD 1 RS-232 AND 1
RS422/485 ON OPTIONAL COMMUNICATIONS CARD)
10 BASE T/100 BASE-TX ETHERNET PORT TO NETWORK UNITS
AND HOST WEB PAGES
USB PORT TO DOWNLOAD THE UNIT'S CONFIGURATION FROM
A PC OR FOR DATA TRANSFERS TO A PC
UNIT'S CONFIGURATION IS STORED IN NON-VOLATILE MEMORY
(8 MBYTE FLASH)
COMPACTFLASH
8.4-INCH TFT DISPLAY (256 COLOR, VGA 640X480 PIXELS)
7-BUTTON KEYPAD FOR ON-SCREEN MENUS
THREE FRONT PANEL LEDS
POWER UNIT FROM 24VDC ±20% SUPPLY
RESISTIVE ANALOG TOUCHSCREEN
CONTENTS OF PACKAGE
- 308 Operator Interface.
- Panel gasket.
- Template for panel cutout.
- Hardware packet for mounting unit into panel.
- Terminal block for connecting power.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other
actuators not equipped with safeguards. To do so can be potentially harmful to
persons or equipment in the event of a fault to the controller.
PART NUMBER
CTVUE-308A
CTVUE-CN00
CTVUE-DN00
CTVUE-RS00
CTVUE-PBDP
CTVUE-CONFIG-CD
CTVUE-PROG
CTVUE-USB
Read complete instructions prior to
installationand operation of the unit.
CompactFlash is a registered trademark of CompactFlash Association.
1
®
SOCKET TO INCREASE MEMORY CAPACITY
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2/CLASS II, DIVISION 2/CLASS III, DIVISION 2
CAUTION: Risk of Danger
Bulletin No. CTVUE-308A-B
Drawing No. LP0716
Released 9/07
CAUTION: Risk of electric shock.

Advertisement

loading

Summary of Contents for Control Techniques 308A

  • Page 1 Released 9/07 Tel +1 952 995 8000 Fax +1 952 995 8099 www.emersonct.com MODEL 308A - GRAPHIC LCD OPERATOR INTERFACE TERMINAL WITH VGA DISPLAY AND TOUCHSCREEN CONFIGURED USING CTVue CONFIGURATOR SOFTWARE UP TO 5 RS-232/422/485 COMMUNICATIONS PORTS (2 RS-232 AND 1 RS-422/485 ON BOARD 1 RS-232 AND 1...
  • Page 2: Specifications

    LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards 3. DISPLAY: IECEE CB Scheme Test Certificate #US/9737/UL CB Scheme Test Report #E179259-V01-S04 308A Issued by Underwriters Laboratories Inc. SIZE 8.4-inch IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment...
  • Page 3: Mounting Instructions

    COMPACTFLASH CARD The 308 is programmed using CTVue Configurator software. The software is available as a free download from Control Techniques’ website, or it can be ordered on CD. Updates to the software for new features and drivers are posted on WARNING - DO NOT CONNECT OR DISCONNECT CABLES the website as they become available.
  • Page 4: Ethernet Communications

    ETHERNET COMMUNICATIONS The Ethernet connector contains two LEDs. A yellow LED in the upper right, and a bi-color green/amber LED in the upper left. The LEDs represent the Ethernet communications can be established at either 10 BASE-T or 100 following statuses: BASE-TX.
  • Page 5 If for any reason you have trouble operating, connecting, or simply have writes data in two minute intervals. Later Microsoft operating systems will questions concerning your new 308, contact Control Techniques’ technical not lock the drive unless they need to write data; Windows 98 may lock the support.
  • Page 6: Compactflash Socket

    CompactFlash can be used for configuration transfers, larger configurations, Control Techniques is also offering a communications card for additional data logging, and trending. RS232 and RS422/485 communications. Visit Control Techniques’ website for information and availability of these cards.