Majestic SA42R Installation Manual page 24

Hide thumbs Also See for SA42R:
Table of Contents

Advertisement

Termination Cap
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm).
Figure 5.13 Installing a TS345/TS345P Square Termination Cap
Majestic Sovereign Series • SA36R/SA42R • Installers Manual • 4010-259 • Rev K • 1/22
24
Place waterproof sealer under
each flange of the termination
cap and on top of each screw
to help prevent leaks.
The last section of pipe must
stop between 2 in. (51 mm)
above the top of the chase and
4 3/4 in. (121 mm) below the
top of the chase.
2 in. (51 mm)
maximum
4 3/4 in. (121 mm)
maximum
Chase
Remove 2 screws
Termination Cap
from front & back
to lift the top off
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Figure 5.14 Installing a TCT375 Terra Cotta Cap
Assemble
storm collar
Termination
around extended
Cap (not shown)
termination cap
pipe
CT
once cap is
installed.
Caulk gaps between
storm collar & pipe,
and storm collar
& chase top.
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Figure 5.15 Installing CT-3A-B Cap Adapter
Figure 5.15 Installing a DTO134/DTO146/DTS134/DTS146 Cap
Place waterproof sealer
under each flange of the
termination cap and on
top of each screw to
help prevent leaks.
The last section of pipe
must stop between 2 in.
(51 mm) above top of
chase and 4-3/4 in. (121
mm) below top of chase
2 in. (51 mm)
4-3/4 in. (121 mm)
Chase
Do NOT block
air holes
Storm Collar
3 clip brackets.
Slip over chase collar
and attach with screws
provided.
The last section of pipe must stop
between 2 in. (51 mm) above the
top of the chase and 4 3/4 in. (121
mm) below the top of the chase.
2 in. (51 mm)
4-3/4 in. (121 mm)
Chase

Advertisement

Table of Contents
loading