Safety Devices - Fujitsu ASBH31KMTA Design & Technical Manual

Table of Contents

Advertisement

11. Safety devices

Type of
protection
Circuit
Current fuse (PCB*)
protection
Fan motor
Thermal protection program
protection
Thermal protection program
(Discharge temp.)
Thermal protection program
Compressor
(Compressor temp.)
protection
Thermal protection program
(Outdoor temp.)
(Only in COOL or DRY mode)
*PCB: Printed Circuit Board
Protection form
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
- 51 -
Model
AOBH31KMTA
250 V, 30 A or 35.5 A
250 V, 3.15 A
250 V, 10 A × 2
150 ±15°C
Fan motor stop
120 ±15°C
Fan motor restart
110°C
Compressor stop
After 7 minutes
Compressor restart
108°C
Compressor stop
80°C or less
Compressor restart
-20°C
Compressor stop
-15°C
Compressor restart
11. Safety devices

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aobh31kmta

Table of Contents