York ZWTA3 Instructions Manual page 37

Table of Contents

Advertisement

Drive Selection
1.
Determine side or bottom supply duct Application.
2.
Determine desired airflow.
3.
Calculate or measure the amount of external static pressure.
4.
Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
2400 CFM
2.
1.6 IWC
3.
Using the supply air blower performance table below, the following data point was located: 1230 RPM & 1.62 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
1.62 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.
1230 RPM is within the range of the 2 HP drives.
7.
Using the 2 HP motor and drive, .5 turns open will achieve 1230 RPM.
Example Supply Air Blower Performance
Air Flow
0.2
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
2100
759
0.65
819
2200
778
0.73
838
2300
797
0.81
857
2400
817
1.90
877
Table X: RPM Selection
Size
Model
HP
(Tons)
1.5
X
Y
2
Johnson Controls Ducted Systems
Available External Static Pressure - IWG
0.4
0.6
0.8
0.77
881
0.87
943
0.84
900
1.95
962
0.92
919
1.03
981
1.01
939
1.12
1002
Max
Motor
Blower
BHP
Sheave
Sheave
1.73
1VL40
2.30
1VP56
1.0
1.2
Standard 1.5 HP & Drive
0.98
1005
1.08
1065
1.18
1.05
1024
1.15
1083
1.25
1.13
1043
1.23
1103
1.33
1.22
1063
1.32
1123
1.42
6 Turns
5 Turns
Open
Open
AK61
N/A
787
AK74
N/A
1035
1.4
1.6
Hi Static 2 HP & Drive
1121
1.28
1172
1.38
1217
1139
1.35
1191
1.45
1236
1159
1.43
1210
1.53
1255
1179
1.52
1230
1.62
1275
4 Turns
3 Turns
2 Turns
Open
Open
Open
847
908
968
1084
1134
1183
5803642-TIM-B-0620
1.8
2.0
1.48
1254
1.59
1.56
1273
1.66
1.64
1292
1.74
1.73
1312
1.83
1 Turn
Fully
Open
Closed
1029
1089
1232
1281
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zw seriesZwta4Zwta5

Table of Contents