Mitsubishi Electric SMART MULTI MXZ-SM36NAM2-U1 Data Book page 20

Hide thumbs Also See for SMART MULTI MXZ-SM36NAM2-U1:
Table of Contents

Advertisement

7. CAPACITY TABLES
<Cooling>
Outdoor Design Dry Bulb Temperature
Total Cooling Load
Room1
Indoor Design Dry Bulb Temperature
Indoor Design Wet Bulb Temperature
Cooling Load
Room2
Indoor Design Dry Bulb Temperature
Indoor Design Wet Bulb Temperature
Cooling Load
<Other>
Indoor/Outdoor Equivalent Piping Length
Capacity of indoor unit
<P•FY series>
Model Number
Model 04 Model 05 Model 06 Model 08 Model 12 Model 15 Model 18 Model 24 Model 27 Model 30 Model 36 Model 48 Model 54 Model 72
for indoor unit
Model
4.0
5.0
Capacity
<M,S,P series>
Model
Capacity class
name
06
09
12
15
SVZ
-
-
12.0
SLZ-KF
-
8.4
11.1
15.0
SEZ-KD
-
8.1
11.5
14.1
MFZ-KJ
-
9.0
12.0
15.0
MLZ-KP
-
9.0
12.0
MLZ-KY
6.0
-
-
MSZ-FH
6.0
9.0
12.0
15.0
MSZ-FS
6.0
9.0
12.0
15.0
MSZ-GL
6.0
9.0
12.0
14.0
MSZ-GS
6.0
9.0
12.0
14.0
MSZ-EF
-
9.0
12.0
15.0
PEAD
-
9.0
12.0
15.0
PLA
-
-
12.0
PAA-A
-
-
-
1. Cooling Calculation
(1) Temporary Selection of Indoor Units
Room1
PEFY-P15
Room2
PEFY-P18
(2) Total Indoor Units Capacity
P15+ P18 = P33
(3) Selection of Outdoor Unit
The P36 outdoor unit is selected as total indoor units capacity is P33
MXZ-SM36NAM2
(4) Total Indoor Units Capacity Correction Calculation
Room1
Indoor Design Wet Bulb Temperature Correction (68.0ºF)
Room2
Indoor Design Wet Bulb Temperature Correction (66.2ºF)
CT
= 32.4 kBtu/h
(5) Outdoor Unit Correction Calculation
Outdoor Design Dry Bulb Temperature Correction (98.6ºF)
Piping Length Correction (250 ft)
= 32.8 kBtu/h
*1 G(CTi) is used only when greater than 100% indoor model size are connected in total,
refer to "7-3. Correction by total indoor".
(6) Determination of Maximum System Capacity
CTi = 32.4 < CTo = 32.8, thus, select CTi.
CTx = CTi = 32.4 kBtu/h
M-P0890
Design Condition
6.0
8.0
12.0
15.0
18
24
30
36
-
18.0
24.0
30.0
36.0
-
-
-
-
17.2
-
-
-
17.0
-
-
-
-
17.2
-
-
-
-
-
-
-
-
17.2
-
-
-
17.2
-
-
-
17.2
22.5
-
-
18.0
22.4
-
-
18.0
-
-
-
18.0
24.0
30.0
36.0
-
18.0
24.0
30.0
36.0
-
18.0
24.0
30.0
36.0
15.0 kBtu/h (Rated)
18.0 kBtu/h (Rated)
36.0 kBtu/h
*1
98.6ºF (37.0ºC)
30.3 kBtu/h
80.6ºF (27.0ºC)
68.0ºF (20.0ºC)
13.6 kBtu/h
75.2ºF (24.0ºC)
66.2ºF (19.0ºC)
16.7 kBtu/h
250 ft
18.0
24.0
27.0
Figure 1 Indoor unit temperature correction
1.02 (Refer to Figure 1)
0.95 (Refer to Figure 1)
Figure 2 Outdoor unit temperature correction
0.98 (Refer to Figure 2)
0.93 (Refer to Figure 3)
Figure 3 Correction of refrigerant piping length
30.0
36.0
48.0
54.0
1.2
1.0
0.8
0.6
0.4
59
60.8
62.6
64.4
66.2
68
69.8
71.6
73.4
15
16
17
18
19
20
21
22
Indoor Temperature
To be used to correct indoor unit only
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
5
14
23
32
41
50
59
68
77
86
95
-15
-10
-5
0
5
10
15
20
25
30
35
Outdoor Temperature
To be used to correct outdoor unit only
Total capacity of indoor unit
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
SMART MULTI
(kBtu/h)
72.0
75.2
[°FW.B.]
23
24
[°CW.B.]
Indoor
Temperature
19.4°C (67.0°F) W.B
[°F D.B.]
104
113
[°C D.B.]
40
45
18 [kBtu/h]
27 [kBtu/h]
36 [kBtu/h]
46.8 [kBtu/h]
550
600
18

Hide quick links: