Toshiba RAS-B07G3KVSG-E Service Manual page 114

Indoor/outdoor unit, r32 or r410a inverter
Hide thumbs Also See for RAS-B07G3KVSG-E:
Table of Contents

Advertisement

11-8-5. Checking Method for Each Part
No.
Part name
1
Electrolytic capacitor
(For raising pressure, smoothing)
2
Converter module
Checking procedure
1. Turn OFF the power supply breaker.
2. Discharge all three capacitors completely.
3. Check that safety valve at the bottom of capacitor is not broken.
4. Check that vessel is not swollen or exploded.
5. Check that electrolytic liquid does not blow off.
6. Check that the normal charging characteristics are show in
continuity test by the tester.
RAS-07, 10, 13J2AVSG-E1
WP-043
C07 → 760µF/ 450V
RAS-16J2AVSG-E1
WP-044
C09, C10 → 760µF/400V
1. Turn OFF the power supply breaker.
2. Discharge all three capacitors completely.
3 Check that the normal rectification characteristics are shown in continuity
test by the tester.
1
2
3
Tester rod
1
2
3
1
- 114 -
Case that product is good
Pointer swings once, and
returns slowly. When
performing test once again
under another polarity, the
pointer should return.
~ ~
+
1 2 3
4
(DB01)
4
Diode check
Resistance value
in good product
4
50kΩ or more
4
(0Ω in trouble)
2
3