York DC180 Installation Manual page 50

R-407c no charge
Table of Contents

Advertisement

5120416-XIM-C-0216
Table 22: Simplicity SE UCB Details (Continued)
RAT+
OAT+
CC1+
EC1+
CC2+
EC2+
RAH+
DCT PRS+
DFS (upper pin)
DFS (lower pin)
APS (up-
per pin)
APS (lower pin)
C
VFD
VFDFLT
50
Description
Return Air Temperature sensor input from 10KΩ
@ 77°F, Type III negative temperature coefficient
thermistor
Outside Air Temperature sensor input from 10KΩ
@ 77°F, Type III negative temperature coefficient
thermistor
#1 refrigerant circuit Condenser Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
#1 refrigerant circuit Evaporator Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
#2 refrigerant circuit Condenser Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
#2 refrigerant circuit Evaporator Coil temperature
sensor input from 10KΩ @ 77°F, Type III negative
temperature coefficient thermistor
Pinned connections on right edge of UCB
Return Air Humidity input from 0-10 VDC @ 0-
100% RH sensor
Supply Duct Pressure input from 0-10 VDC @ 0-
5" w.c. sensor
24 VAC hot return from Dirty Filter Switch
24 VAC hot out for Dirty Filter Switch
24 VAC hot return from Air Proving Switch
24 VAC hot out for Air Proving Switch
Common for the VFD output
2-10 VDC (0-100%) output for the indoor blower
Variable Frequency Drive
24 VAC hot input from the normally open VFD
alarm contact
Function & Comments
Input required for operation; 3.625 VDC reading RAT+ to RAT–
with open circuit. Used in return air enthalpy calculation.
Substitutes for space temperature if no other space
temperature input is present.
Input required for operation but may be a communicated value;
3.625 VDC reading OAT+ to OAT– with open circuit. Used in
heat/cool cutouts, low ambient cooling determination, dry bulb
free cooling changeover, outside air enthalpy calculation,
economizer loading operation, heat pump demand defrost
calculation.
Input required for heat pump units, not required for A/C units;
3.625 VDC reading CC1+ to
CC1– with open circuit. Used in heat pump demand defrost
calculation.
Input required for operation; 3.625 VDC reading EC1+ to EC1–
with open circuit. Used in suction line temperature safety.
Input required for 2-compressor heat pump units, not required
for 2-compressor A/C units, not active for 1-compressor units;
3.625 VDC reading CC2+ to CC2– with open circuit. Used in
heat pump demand defrost calculation.
Input required for operation of 2-compressor units, not active for
1-compressor units; 3.625 VDC reading EC2+ to EC2– with
open circuit. Used in suction line temperature safety.
Input required for reheat units, optional in all other units, may be
a communicated value. Used in return air enthalpy calculation,
temperature/humidity setpoint reset, reheat operation.
Input required for variable air volume units. Used in VAV indoor
blower operation.
Optional input; switch closure for greater than 15 seconds
during indoor blower operation
initiates a notification alarm
Connects through circuit trace to the R terminal
When this optional input is enabled: the air proving switch must
close within 30 seconds
of initiation of indoor blower operation and not open for greater
than 10 seconds during in- door blower operation to allow heat/
cool operation and prevent an "APS open" alarm; the air proving
switch must open within 30 seconds of termination of indoor
blower operation to prevent an "APS stuck closed" notification
alarm
Connects through circuit trace to the R terminal
Negative of the VDC circuit for the VFD output
Output is active with indoor blower operation. For CV units: this
output provides stepped IntelliSpeed control of the indoor
blower VFD based on fan-only, cooling stage and heating stage
outputs. For VAV units: this output provides control of the indoor
blower VFD based on supply duct static pressure input and
setpoint.
The VFD alarm contact switches from R within the unit wiring
harness. 24 VAC input results in unit shutdown and a "VFD
fault" alarm