Supply Air Blower Performance (15 Ton) - Gas Heat 180 Mbh - Bottom Duct Connections
MOTOR
BLOWER
PULLEY
SPEED,
(TURNS
(RPM)
ESP
OPEN)*
(Pa)
3
HIGH STATIC DRIVE (m
/s)
1030
6.0
378
1070
5.0
417
1115
4.0
461
1155
3.0
502
1200
2.0
548
1240
1.0
590
MOTOR
BLOWER
PULLEY
SPEED,
(TURNS
(RPM)
ESP
OPEN)*
(iwg)
HIGH STATIC DRIVE (CFM)
1030
6.0
1.5
1070
5.0
1.7
1115
4.0
1.9
1155
3.0
2.0
1200
2.0
2.2
1240
1.0
2.4
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static
High efficiency single package air conditioners and single package gas/electric units 6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 nominal tons 10.0-11.5 eer (48 pages)