Carrier AGAGC9NPS01B Installation Instructions Manual page 7

Gas conversion kit
Table of Contents

Advertisement

AGAGC9NPS01B Gas Conversion Kit, Natural to Propane: Installation Instructions
Two Stage Gas Valve
Refer to
Fig. 12
and
Fig.
13.
TWO-STAGE
TWO-STAGE
ON/OFF Switch
ON/OFF Switch
1/2" NPT Inlet
1/8" NPT Inlet
1/8" NPT Inlet
Pressure Tap
Pressure Tap
Fig. 12 – Automatic Gas Valve (Two-Stage) without Tower Pressure
MANIFOLD PRESSURE TAP SET SCREW:
3/32" HEX HEAD ACCEPTS
INLET PRESSURE TAP
SET SCREW: 3/32" HEX HEAD
ACCEPTS 5/16" HOSE
CONNECTION
1/2" NPT
INLET
ON/OFF SWITCH
Representative drawing only, some models may vary in appearance.
1/8" NPT
INLET
PRESSURE
TAP
INP
1/2" NPT
INLET
Representative drawing only, some models may vary in appearance.
Fig. 13 – Automatic Gas Valve (Two-Stage) with Tower Pressure
1. Remove caps that conceal adjustment screws for high heat and low
heat gas-valve regulators (see
2. Remove the high heat and low heat regulator adjustment screws.
3. Remove the high heat and low heat regulator springs (silver).
4. Install the high heat and low heat propane gas regulator springs
(white).
5. Install the high heat and low heat regulator adjustment screws.
6. Turn high heat stage adjusting screw clockwise (in) 13.5 full turns.
This will increase the manifold pressure closer to the propane set
point.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Regulator Seal Cap
Regulator Seal Cap
Regulator Adjustment
Regulator Adjustment
Screw
Screw
Regulator Spring
Regulator Spring
1/2" NPT Outlet
1/2" NPT Outlet
1/8" NPT Manifold
1/8" NPT Manifold
Pressure Tap
Pressure Tap
Ports
REGULATOR SEAL CAP
(REGULAR ADJ. UNDER CAP)
5/16" HOSE CONNECTION
OUTP
1/2" NPT
OUTLET
Ports
Fig. 12
and
Fig.
13)
7. Turn low heat stage adjusting screw clockwise (in) 9.5 full turns.
This will increase the manifold pressure closer to the propane low
heat set point.
8. Do not install regulator seal caps at this time.
Modulating Gas Valve
Refer to
Fig. 14
A11472
NOTE: The Propane jumper for the modulating gas valve is very small.
A170117
Needle-nose pliers are required to insert the jumper into the valve. If the
jumper is not installed, the valve will not operate properly on propane.
1. Locate the round "NAT GAS" sticker on the top of the gas valve.
2. Peel the sticker off and discard.
3. Note the small square opening in the top of the gas valve.
4. Note the two jumper pins inside the modulating gas valve.
5. Remove the small black plastic propane jumper from the envelope.
6. Use needle-nosed pliers to hold the jumper by the tab on the end.
7. Insert the jumper on the pins inside the gas valve.
8. Cover the opening in the gas valve with the label marked "LP
1/2" NPT
GAS"
OUTLET
A170132
Inlet
Pressure Tap
7
through
Fig.
16.
Fig. 14 – Propane Jumper
Fig. 15 – Installing Propane Jumper
MODULATING
ON/OFF Switch
Turn screw 1 click per
second to adjust rate.
Clockwise to increase
rate, counter clockwise
to decrease rate.
Manifold
Pressure Tap
A11373
A11375
Min/Max Heat Adust
(Under Cap)
1/2" NPT Outlet
A10496