6.3

Opening the burner

Disconnect the electrical supply from the burner by
means of the main system switch.
DANGER
Turn off the fuel interception tap.
DANGER
Wait for the components in contact with heat sourc-
es to cool down completely.
6.4

Closing the burner

In order to close the burner, re-install all components with reverse
procedure:
 remove the 2 extensions 9) and re-screw the screws 8) on the
sliding bars 4) ;
 push the burner up to approximately 4" from the pipe coupling;
 reinsert the electrode lead and slide the burner as far as the
stop.
 fix the screws 3) to secure the burner to the combustion head;
 fix the 4 screws 1) to install the cover 2).
Maintenance
9
8
2
1
31
In order to open the burner, proceed as follows:
 loosen the 4 screws 1) (Fig. 40) and remove the cover 2);
 install the 2 extensions 9) on the sliding bars 4) and re-screw
the screws 8);
 remove the screws 3) and pull back the burner on the sliding
bars 4) of about 4";
 disconnect the electrode lead, then unthread the burner com-
pletely from the sliding bars;
 remove the screw 6) and extract the inner part 5) of the head.
After carrying out maintenance, cleaning or check-
ing operations, reassemble the hood and all the
safety and protection devices of the burner.
6
4"
4
1
3
7
D10595
5
Fig. 40
20028248