Section 3: Programming Options - Honeywell SILENT KNIGHT SK-PS6 Instruction Manual

Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature or option
Door Holder Dropout Delay
AC Loss Delay Timer
Operating Mode
1
A two hour delay is only permitted on an addressable FACP.
2
For site compliance to UL864 10th Edition, all power supplies must be configured for Default Mode.
This section describes the programming options available via DIP switch settings. The SK-PS can be field programmed using DIP switches
S1-S8 which are located at the bottom of the circuit board. S1 controls the global options of the power supply and S2-S8 control the functions
of each output circuit, respectively. Refer to the following illustration for switch locations and DIP switch placement in the ON and OFF
positions.
Important: Activate output DIP switch changes by setting S1 positions 9 and 10 appropriately. Refer to Table 3.8 on page 27 for DIP Switch
programming settings.
TB15
S1
ON
1 2 3 4 5 6 7 8 9 10
Switches 1 through 9 shown
SK-PS Series Instruction Manual — P/N LS10227-002SK-E:C 2/2/2022

Section 3: Programming Options

Permitted in
UL864 / UL2572? (Y/N)
Y
Y
Y
Table 3.1 Agency-Permitted Programming Settings
in OFF (Open) position
Switch 10 shown in
ON (Closed) position
Figure 3.1 Field Programming DIP Switches
Possible settings
Refer to "AC Loss Door Holder Dropout Timer" on
page 25.
• Does not drop
• 15 seconds
• 5 minutes
• 60 seconds
Refer to "AC Fail Indication Delay" on page 26.
• 30 hours
• 12 hours
• 2 hours
• none
Refer to "Operating Modes" on page 26.
• Retrofit Mode
• Change Output Circuit Configurations
• Display Trouble History
• Default Mode
S2-S8
ON
1 2 3 4 5 6 7 8
Switches 1 through 7 shown
Settings permitted in
UL 864 / UL2572
• Does not drop
• 15 seconds
• 60 seconds
• 5 minutes
• 2 hours
• none
• Default Mode
in OFF (Open) position
Switch 8 shown in
ON (Closed) position
1
2
23