FACP with SK-PS Power Supply in Slave Configuration

2.5 FACP with SK-PS Power Supply in Slave Configuration
In this application, the power supply is configured as a Slave unit and connected to a master FACP programmed for synchronized output. .
TB15
The following notes apply to Figure 2.7 on page 17
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
3.
Set Output DIP Switch: position 3=ON, 4 = OFF, 5 = ON, 6 = OFF.
4.
If the FACP has a dedicated sync output connector, wire the remote sync output connector to Input #1 terminals 2 and 3.
5.
In this example, the output is mapped to Input#1 in Slave Configuration, but it can programmed to another input using the DIP switches.
6.
For NFPA 72 compliance, notification appliances cannot be installed on the FACP control circuit connecting to the SK-PS input
circuits.
2.6 SK-PS Power Supply in Master Configuration Connected to FACP
In this application, a master SK-PS power supply, set for synchronization, is connected to an FACP with non-synchronized output.
TB15
The following notes apply to Figure 2.8.
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Set Output DIP switches to the desired sync protocol as described below. Refer to the Device Compatibility Document for devices.
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
SK-PS Series Instruction Manual — P/N LS10227-002SK-E:C 2/2/2022
SK-PS
Figure 2.7 Supervised Master/Slave Connections
SK-PS
Figure 2.8 Supervised FACP to Master Connections (non-synchronized source)
DIP Switch Position
3
4
5
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
ELR for
FACP
NAC
ELR for
FACP
NAC
Synchronization Type
6
OFF
Master Configuration - ANSI Temporal (Temporal 3)
OFF
Master Configuration - CO Temporal (Temporal 4)
ON
Master Configuration - Amseco/Potter
ON
Master Configuration - Gentex
ON
Master Configuration - System Sensor
ON
Master Configuration - Wheelock
ON
Master Configuration, Selective Silence - Amseco/Potter
ON
Master Configuration, Selective Silence - Gentex
ON
Master Configuration, Selective Silence - System Sensor
ON
Master Configuration, Selective Silence - Wheelock
NAC programmed for sync
or remote sync output
FACP
NAC with no synchronization
NAC1
FACP
(also can be triggered by a
control module or relay module)
Installation
17