Table 1B — Physical Data — 575J*16-25 Units — 60 Hz SI
UNIT SIZE 575J*
NOMINAL CAPACITY (kW)
REFRIGERANT SYSTEM
Refrigerant
# Circuits / # Compressor / Type
Shipping Charge A/B (kg)
Operating Charge w/Fan Coil
Metering Device
High---Pressure Trip / Reset (kPa)
Low---Pressure Trip / Reset (kPa)
COMPRESSOR
Model
Oil Charge A/B (L)
Speed (r/s)
OUTDOOR COIL
Material
Coil Type
Rows/Fins Per Meter (Fins/m)
2
Total Face Area (m
)
OUTDOOR FAN / MOTOR
Qty / Motor Drive Type
Motor HP / r/s
Diameter (mm)
Nominal Airflow (L/s)
Watts (Total)
Cut-in
PIPING CONNECTIONS (mm ODS)
Qty / Vapor
Qty / Liquid
LEGEND
NEMA — National Electrical Manufacturers Association
ODS — Outside Diameter Sweat (socket)
† Approximate system charge with 7.6 m piping of sizes indicated with matched 524J***H
16
15
Puron
R
(R--- 410A)
2 / 2 / Scroll
4.1/4.1
A/B (kg)
9.5/9.5
Acutrol
4344 / 3482
372 / 807
ZP83 (2)
1.7
58
Al/Cu
Round Tube/Plate Fin (RTPF)
2/17
4.4
3 / Direct
¼ / 18
559
4719
970
44 5
2 / 34.9
2 / 12.7
6
25
20
2 / 2 / Scroll
4.1/4.1
12.2/12.2
Acutrol
4344 / 3482
372 / 807
ZP103 (2)
3.2
58
4.6
4 / Direct
¼ / 18
559
6607
1150
44 5
2 / 34.9
2 / 12.7