Bryant 575Jx08G/H Series Installation, Start-Up And Service Instructions Manual
Bryant 575Jx08G/H Series Installation, Start-Up And Service Instructions Manual

Bryant 575Jx08G/H Series Installation, Start-Up And Service Instructions Manual

Heat pump condensing units, 60 hz, single circuit, 2-stage with digital scroll compressor and puronr (r-410a) refrigerant - size 08

Advertisement

575J*08G/H
HEAT PUMP CONDENSING UNITS, 60 Hz,
SINGLE CIRCUIT, 2- - STAGE WITH DIGITAL SCROLL COMPRESSOR
R
AND PURON
(R- - 410A) REFRIGERANT - - SIZE 08
CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation, Start- -Up and
Service Instructions
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
5 - - 14
. . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
. . .
. . . . . . . . . . . . . . . . . . . .
15 - - 18
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
5
5
6
6
6
6
9
9
14
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
15
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
19
APPENDIX A
19
19
19
19
19
APPENDIX C
20
20
20
20
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . .
21 - 32
21
21
21
21
21
21
22
22
22
22
28
30
30
32
32
33
R
-
34
34
34
39 - - 40

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 575Jx08G/H Series

  • Page 1: Table Of Contents

    575J*08G/H HEAT PUMP CONDENSING UNITS, 60 Hz, SINGLE CIRCUIT, 2- - STAGE WITH DIGITAL SCROLL COMPRESSOR AND PURON (R- - 410A) REFRIGERANT - - SIZE 08 Installation, Start- -Up and Service Instructions CONTENTS SAFETY CONSIDERATIONS ....SERVICE .
  • Page 2: Safety Considerations

    SAFETY CONSIDERATIONS WARNING Improper installation, adjustment, alteration, service, ELECTRICAL SHOCK HAZARD maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal Failure to follow this warning could cause personal injury or property damage. Consult a qualified installer, injury or death.
  • Page 3: Rated Indoor Airflow (Cfm)

    10 11 12 13 14 15 16 17 Example 5 7 5 J E 0 8 G 0 0 0 A 0 0 A 0 A Model Type Packaging 575J = Bryant Heat Pump A = Standard Condensing Unit with B = LTL Puron ®...
  • Page 4 Standard Corner Corner Corner Corner Center of Gravity Unit Height Weight UNIT lbs. lbs. lbs. lbs. lbs. 50-3/8 575J*08G/H [533] [610] [584] [1280] C14310 Fig. 2 - - 575J*08G/H Unit Dimensions...
  • Page 5: Installation

    Table 1 – Physical Data Table 2 – Physical Data 575J*08G/H — 60 Hz English 575J*08G/H — 60 Hz SI NOMINAL CAPACITY (tons) NOMINAL CAPACITY (kW) 26.4 OPERATING WEIGHTS (lb) OPERATING WEIGHTS (lb) Round Tube/Plate Fin Coil (Cu/Al) Round Tube/Plate Fin Coil (Cu/Al) ‡...
  • Page 6: Step 2 - Complete Pre-Installation Checks

    Step 3 — Prepare Unit Mounting Support have one of each type in opposite modes. Relocate sections to minimize the length of interconnecting tubing. Slab Mount — Provide a level concrete slab that extends a minimum of 6 DO NOT BURY REFRIGERATION LINES. in.
  • Page 7 Charge Charge Quantity, lbs. NOTE: For applications with linear length greater than 100 ft (30.5 m), contact your local Bryant representative. Refrigerant Line Sizing — Table 4 – Maximum Vapor Line Sizes Consider the length of the piping required between the...
  • Page 8 — The stub tube connections include -in SAE service fittings Install Liquid Line Solenoid Valves with Schrader valve cores (see Fig. 5). Before making any It is recommended that a bi-directional solenoid valve be brazed connections to the unit service valves, remove both placed in the main liquid line (see Fig.
  • Page 9: Step 6 - Install Accessories

    For linear line lengths longer than 100 ft (30.5 m), contact contactor C or optional disconnect switch. These leads are your local Bryant representative for system charge value. for factory run-test purposes only; remove and discard Step 6 — Install Accessories before connecting field power wires to unit connection points.
  • Page 10 WARNING FIRE HAZARD Failure to follow this warning could result in intermittent operation or performance satisfaction. Do not connect aluminum wire between disconnect switch and condensing unit. Use only copper wire. (See Fig. 6.) ELECTRIC C12284 DISCONNECT Fig. 8 - - Location of Non- - Fused Disconnect Enclosure SWITCH COPPER To field install the NFD shaft and handle:...
  • Page 11 Such operation would invalidate box access panel. See Fig. 10. any applicable Bryant warranty. The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option.
  • Page 12 Fig. 13 depicts typical connections to a Bryant power to the unit. Treat all units as electrically energized 524J fan coil unit. Plan for field connections carefully and until the convenience outlet power is also checked and install control wiring correctly per the project plan.
  • Page 13 Control transformer TRAN2 provides control power through terminal A1 (9) to C for the liquid line solenoid. Maximum available power is 15 va. This output is switched ON/OFF by the Solenoid Valve Relay (field-supplied, use Bryant Service Part PNO HN61PC005).
  • Page 14: Step 8 - Wind Baffles For Low Ambient Control

    Table 8 – Electrical Data — 575J*08G/H 60 Hz Units WITH POWERED CONVENIENCE OUTLET VOLTAGE POWER COMPRESSOR OFM (ea) DISCONNECT SIZE RANGE SUPPLY UNIT V ---Ph---Hz MOCP 208/230--- 3--- 60 25.1 460--- 3--- 60 12.8 575J*08G/H 575--- 3--- 60 10.1 WITHOUT POWERED CONVENIENCE OUTLET VOLTAGE POWER...
  • Page 15: Pre-Start-Up

    PRE-START-UP CAUTION IMPORTANT: Before beginning Pre-Start-Up or UNIT DAMAGE HAZARD Start-Up, review Start-Up Checklist at the back of this book. The Checklist assures proper start-up of a Failure to follow this caution may result in equipment damage. unit and provides a record of unit condition, application requirements, system information, and Prior to starting compressor, a preliminary charge of operation at initial start-up.
  • Page 16 The unit must be charged in Cooling mode only. Refer to Cooling Charging Chart, Fig. 16. For applications with line lengths greater than 100 ft, contact Bryant representative. Vary refrigerant until the conditions of the chart are met. The charts are based on charging the units...
  • Page 17 7.5 TON DUAL STAGE CHARGING CHART PURON COMPRESSOR FULL LOAD, ALL CONDENSER FANS OPERATING DIAGRAMME DE REMPLISSAGE DE PURON POUR 7.5 TONNES, 2 STAGE COMPRESSEUR À PLEINE CAPACITÉ, TOUS LES VENTILATEURS DU CONDENSEUR EN OPÉRATION PRESSURE AT LIQUID VALVE (PSIG) PRESSION À...
  • Page 18 C14303 Fig. 17 - - Typical 575J*08G/H Wiring Diagram - - 208/230V- - 3PH- - 60Hz Unit Shown...
  • Page 19: Operating Sequence

    OPERATING SEQUENCE Reversing valve solenoid (RVS) is energized in Cooling modes. This solenoid will remain energized until the next Base Unit Controls Heating mode is initiated. Cooling, Unit With Economizer — Indoor (Supply) Fan — Refer to fan coil unit installation instructions and The indoor fan contactor (IFC) is remotely located at the economizer accessory...
  • Page 20: Supplemental Heating/Emergency Heating

    ROUTINE SYSTEM MAINTENANCE If the outdoor coil’s Defrost Thermostat switch (DFT) is closed (shorting DFB terminals DFT1 and DFT1), the Defrost cycle will start. Output at OF is removed; outdoor These items should be part of a routine maintenance fans stop during the Defrost cycle. Output P3–7 (RVS1) is program, to be checked every month or two, until a specific energized;...
  • Page 21: Service

    SERVICE 3. Place terry cloth shop towel inside unit immediately under component(s) to be serviced and prevent lubric- Refrigeration System ant run-offs through the louvered openings in the base pan. CAUTION 4. Perform required service. 5. Remove and dispose of any oil contaminated material per local codes.
  • Page 22: Refrigerant System Pressure Access Ports

    SEAT CORE (Part No. EC39EZ067) 1/2-20 UNF RH 0.596 45° 30° WASHER DEPRESSOR PER ARI 720 O-RING 1/2" HEX +.01/-.035 5/8” HEX FROM FACE OF BODY This surface provides a metal to metal seal when 7/16-20 UNF RH torqued into the seat. Appropriate handling is required to not scratch or dent the surface.
  • Page 23 Table 9 – 575J Defrost Board I/O and Jumper Configurations Inputs Point Name Type of I/O Connection Pin Number Unit Connection Note G Fan DI, 24-vac P2-3 Not used Y1 Cool 1 DI, 24-vac P2-5 TB-Y1 W1 Heat 1 DI, 24-vac P2-7 TB-W1 R Power...
  • Page 24 positions of DIP switches SW1 and SW2 (see Fig. 21 and Table 10). The default run period is 60 minutes. C10790 Fig. 21 - - DIP Switch Settings — Defrost Board Switches At the end of the continuous run period, the defrost control will test for a need to defrost.
  • Page 25 Defrost Speedup Functions — The DFB permits the servicer to speed-up the defrost cycle. There are two speed-up sequences: relative speed-up and an immediate forced defrost. Speed-up sequences are initiated by shorting jumper wires JMP17 and JMP18 together (see Fig. 20); use a straight-edge screwdriver.
  • Page 26 Fans Service Valves C14305 Fig. 23 - - 575J*08G/H Exterior...
  • Page 27 Outdoor Coil Defrost Thermostat (DFT) High Flow Access Ports C14306 Fig. 24 - - 575J*08G/H Interior...
  • Page 28: Comfort Alert Diagnostic Module

    COMFORT ALERT DIAGNOSTIC The POWER LED indicates the presence of control power to the CADM. MODULE POWER The Comfort Alert Diagnostic Module (CADM) monitors (GRN) and analyzes data from the Copeland Scroll three-phase compressor and the thermostat demand. The CADM also provides a 3-minute anti-recycle time delay to compressor cycling.
  • Page 29 Table 11 – LED Status Codes Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Compressor protector is open Red “TRIP” LED On Solid Thermostat demand signal Y is present, but the Condensing unit power disconnect is open compressor is not running.
  • Page 30: Lubrication

    Table 12 – CADM Troubleshooting Miswired Module Indication Recommended Troubleshooting Action Green LED is not on, Determine if both R and C module terminals are connected. Verify voltage in module does not power up present at module’s R and C terminals. NOTE: The CADM requires a constant nominal 24VAC power supply.
  • Page 31 CAUTION CAUTION PERSONAL INJURY AND UNIT DAMAGE UNIT RELIABILTY HAZARD HAZARD Failure to follow this caution may result in reduced Failure to follow this caution may result in personal unit performance . injury or equipment damage. High velocity water from a pressure washer, garden Only approved cleaning is recommended.
  • Page 32: Service Parts

    Service Parts 5. Mix Totaline environmentally sound coil cleaner in a gallon garden sprayer according to the instruc- Listings of service parts for all units are available from the tions included with the cleaner. The optimum solution Replacement Components Division’s Electronic Parts temperature is 100F (38C).
  • Page 33: Troubleshooting

    TROUBLESHOOTING PROBLEM CAUSE REMEDY Compressor and Power failure. Call power company. Outdoor Fan Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Determine root cause. Will Not Start. Defective thermostat, contactor, transformer, Replace component. control relay, or capacitor. Insufficient line voltage.
  • Page 34: Air Conditioner And Heat Pump With Puron

    APPENDIX A APPENDIX B  Air Conditioner & Heat Pump with PURON Wiring Diagram List — Quick Reference Guide Electrical Diagram Unit Characteristics Number S Puron (R-410A) refrigerant operates at 50 percent to 208/230---3---60 38AU000181 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are 460---3---60 38AU000183...
  • Page 35 Troubleshooting — Wind baffles are required to prevent wind cross currents from causing abnormally low condensing temperatures. OBSERVATION POSSIBLE REMEDY Use 20- - gauge sheet metal to fabricate wind baffles (see Check power & wiring Check sensor location Fig. 29 and Table 14). Fans won’t start Check sensor resistance Check OFR...
  • Page 36 C10800 Fig. 29 - - Wind Baffles...
  • Page 38 Catalog No: II575J---08G ---H ---01 Copyright 2014 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 11/14 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 39: Start Up Checklist

    START UP CHECKLIST I. PRELIMINARY INFORMATION OUTDOOR: MODEL NO. SERIAL NO. INDOOR: MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-START-UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
  • Page 40 NOTES: Catalog No: II575J---08G ---H ---01 Copyright 2014 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 11/14 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents