Daikin Hubbard GCU2040PXB1 Installation, Commissioning And Maintenance Manual page 168

Table of Contents

Advertisement

Refrigerant fluid
Product Model
Item
Evaporating temp.
Annual electricity consumption
Seasonal Energy Performance Ratio
Parameters at full load and ambient temperature 32°C (Point A)
Rated cooling capacity
Rated power input
Rated COP
Parameters at full load and ambient temperature 25°C (Point B)
Rated cooling capacity
Rated power input
Rated COP
Parameters at full load and ambient temperature 15°C (Point C)
Rated cooling capacity
Rated power input
Rated COP
Parameters at full load and ambient temperature 5°C (Point D)
Rated cooling capacity
Rated power input
Rated COP
Parameters at full load and ambient temperature 43°C
Rated cooling capacity
Rated power input
Rated COP
Capacity control
Coefficient of degradation for fixed and
staged capacity units*
Copyright HPL March 2021
ECO Design
Directive 2009/125/EC
R744 (CO
GCU2040PXB1
Symbol
Value
t
-10
Q
12,307
3.24
SEPR
P
6.5
A
D
3.81
A
COP
1.70
A
P
5.83
B
D
2.7
B
COP
2.160
B
P
4.82
C
D
1.6
C
COP
3.01
C
P
4.02
D
D
0.90
D
COP
4.46
D
P
4.00
3
D
4.51
3
COP
0.89
3
Variable speed
Cd
0.25
Page 168 of 172
)