ENG
Mask index
Display description
Fca01
Address
Protocol
Baudrate
Fd01
Insert password
Fd02
Logout
Fd03
User
Service
Manufacturer
Fda01
Enable CpCOe
Offl ine pattern
Digital Output pattern 1: ... 6: Digital output status when expansion card offl ine
Fda02
Universal Input pattern
UI01..UI10
The following parameters refer to line 2, for details, see the corresponding parameters for line 1 above
Fcb01
Address
Protocol
Baudrate
Mask index
Display description
G.Safeties
Gba01
Enable prevent
Gba02
Setpoint
Diff erential
Decrease compressor power
time
Gba03
Enable heat recov. as fi rst
prevent step
Off set HeatRecov
Gba04
Enable ChillB. as fi rst prevent
step
Chill. off set
Gba05
Max. num prevent
Prevent max number
evaluation time
Reset automatic prevent
Gca01
Common HP type
Common HP delay
Gca02
Common LP start delay
Common LP delay
Gca03
Time of semi-automatic
alarm evaluation
Numer of retries before alarm
becomes manual (line 1)
Gca04
Liquid alarm delay
Oil alarm delay
Gca05
Output relay alarm activation
with
The following parameters refer to line 2, for details, see the corresponding parameters for line 1 above
Gbb01
Enable prevent
...
...
Gcb01
Common HP type
Common HP delay
...
...
Mask index
Display description
H.Info
H01 (display
Ver.
Bios
only)
Boot
H02 (display
Board type
Size
only)
FLASH mem
RAM
Built-in type
Cycle time
Copyright HPL March 2021
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Description
Address of the supervisory system (line 1)
Supervisor communication protocol (line 1)
Supervisor communication speed (line 1)
Password
Current password level
Logout
User password
Service password
Manufacturer password
Enable expansion card
Enable output confi guration when offl ine
Analogue output status when expansion card offl ine
Address of the supervisory system (line 2)
Supervisor communication protocol (line 2)
Supervisor communication speed (line 2)
Description
Enable high pressure condensing prevent (line 1)
High pressure condensing prevent threshold (line 1)
High pressure condensing prevent diff erential (line 1)
Decreasing compressor capacity time (line 1)
Enabling heat recovery as fi rst stage for condensing HP prevent (line 1)
Off set between heat recovery and prevent setpoint (line 1)
Enable ChillBooster as fi rst stage for condensing HP prevent (line 1)
Off set between ChillBooster and prevent setpoint (line 1)
Max number of prevent before locking compressors (line 1)
Prevent max number evaluation time
Reset maximum number of prevent (line 1)
Type of reset for common HP alarm (line 1)
Common high pressure delay (line 1)
Common low pressure delay at startup (line 1)
Common low pressure delay during operation (line 1)
Number of LP interventions evaluation time (line 1)
Number of LP interventions in the period after which the alarm becomes a manual reset
(line 1)
Liquid level alarm delay (line 1)
Common oil alarm delay (line 1)
Selection of output relay alarm activation with active alarms or alarms not reset
Enable high pressure condensing prevent (line 2)
...
Type of reset for common HP alarm (line 2)
Common high pressure delay (line 2)
...
Description
Software version and date
Bios version and date
Boot version and date
Hardware type
Hardware size
Flash memory size
RAM memory size
Built-in display type
Number of cycles per second and cycle time software
72
Page 121 of 172
Def.
U. of M.
Values
196
---
0...207
Carel slave
---
--, CAREL SLAVE
local
LOCAL
CAREL SLAVE
REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
19200
---
1200...19200
0000
---
0...9999
---
---
User | Service |
Manufacturer
NO
---
NO | YES
0000
---
0...9999
1234
---
0...9999
1234
---
0...9999
NO
---
YES | NO
Disabled
---
Abled | Disabled
OFF
---
ON | OFF
0
%
0...100
196
---
0...207
pRack
---
---, CAREL SLAVE
manager
LOCAL
CAREL SLAVE
REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
19200
---
1200...19200
Tab. 7.g
Def.
U. of M.
Values
NO
---
NO | YES
0.0 barg
...
... (**)
0.0 barg
...
0.0...99,9
0
s
0...999
NO
---
NO | YES
0.0 barg
...
0.0...99,9
NO
---
NO | YES
0.0 barg
...
0.0...99,9
3
---
1...5
60
h
0...999
NO
---
NO | YES
AUTO
---
AUTO | MAN
10
s
0...999
60
s
0...999
20
s
0...999
120
min
0...999
5
---
0...999
0
s
0...999
0
s
0...999
alarms attivi
alarms attivi
alarms no reset
NO
---
NO | YES
...
...
...
AUTO
---
AUTO | MAN
10
s
0...999
...
...
...
Tab. 7.h
Def.
U. of M.
Values
...
---
...
...
---
...
...
---
...
...
---
...
...
---
...
---
kB
...
---
kB
...
---
---
None | pGDE
---
cicli/s / ms ...
Tab. 7.i
P4114S Rev 03