Drain pan heater

Advertisement

DRAIN PAN HEATER INSTALLATION
Step 4, continued
Figure 9: Form heater element and extend ends through the knockouts at bottom of ODU (8 - 20 Ton).
Attach the heater element using
the clamps (10 places) and
self-drilling screws provided.
Figure 10: Multi V 5 ODU Service Ports.
Liquid Pipe
Pipe Not Used for
Heat Pump Systems
(Keep Closed
and Capped)
Vapor Pipe
Turn off power to outdoor unit before installation.
Electric shock can cause physical injury or death.
Do not puncture the outdoor unit coil or other interior components when drilling holes for the screws.
If there is a hole in the outdoor unit coil, there is a risk of refrigerant leak. Exposure to high concentration levels of refrigerant gas may lead to
illness or death.
18
8-20 Ton Multi V 5 ODU bottom view.
Route heater element along the taped path not allowing the element
to have direct, physical contact with the base pan paint surface.
Service Ports
Top view of knockoputs inside ODU
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Six inches from each end of the
element are not heated. Run
rubber ends through knockouts
into the inside of the ODU
in the vertical position as shown.

Advertisement

loading

This manual is also suitable for:

Multi v 5Zplt1a52aZplt2a51aZplt2a52a