NFPA 72 Auxiliary Fire Alarm System
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the MRP-2002/E main circuit board to supervise placement of the
4XTMF module.
2. Refer to "4XTMF Transmitter Module Installation" on page 29 for detailed information.
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver
Model RS82.
Figure C.3 Remote Station Connection Using 4XTMF Module
NFPA Standard-Specific Requirements
Polarity Shown is
+
-
Normal Standby
+
Power-limited
-
Ω
(Dummy load with a 4.7K
resistor when no connection is made)
4XTMF Transmitter Module
, ¼ watt