Fujitsu AOU42RGLX Design & Technical Manual page 70

Hide thumbs Also See for AOU42RGLX:
Table of Contents

Advertisement

3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function number
22
4) Vertical airflow direction range control
To prevent draft, change the setting to "Upward" (01).
Note that the airflow in certain usage conditions may leave the ceiling dirty. In such cases, the use of
the optional Panel spacer is recommended.
Function number
23
5) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er's recommended value).
Function number
30
(For cooling)
9-2. Contents of function setting
Setting value
00
01
Setting value
00
01
Swing scope (standard)
Setting value
00
01
02
03
04
05
06
07
08
31
(For heating)
09
10
11
12
13
14
15
16
17
Setting description
4-way
3-way
Setting description
Standard
Upward
Ceiling
Swing scope (upward)
Setting description
Standard setting
No correction 0.0 °F (0.0 °C)
-1 °F (-0.5 °C)
-2 °F (-1.0 °C)
-3 °F (-1.5 °C)
-4 °F (-2.0 °C)
-5 °F (-2.5 °C)
-6 °F (-3.0 °C)
-7 °F (-3.5 °C)
-8 °F (-4.0 °C)
+1 °F (+0.5 °C)
+2 °F (+1.0 °C)
+3 °F (+1.5 °C)
+4 °F (+2.0 °C)
+5 °F (+2.5 °C)
+6 °F (+3.0 °C)
+7 °F (+3.5 °C)
+8 °F (+4.0 °C)
- 64 -
Factory setting
Factory setting
Factory
setting
More cooling
Less heating
Less cooling
More heating
9. Function settings